Upgrade the Series 9000 target definition

When importing an
AADvance® Workbench
version 1.1 or version 1.2 project, upgrade the Series 9000 target definition.
IMPORTANT: When using
AADvance® Workbench
software to import a project with its library, and if the Series 9000 target definition is not up-to-date, see Importing an AADvance Project with Library with outdated Series 9000 Target Definition.
To upgrade the Series 9000 target definition
  1. Import an
    AADvance Workbench
    version 1.1 or version 1.2 project.
    A subfolder for the imported project is created in the
    AADvance
    projects folder on your hard drive. The default
    AADvance
    projects folder path is %USERPROFILE%\Documents\SIS Workstation
    <version>
    \Projects.
  2. Exit the
    AADvance-Trusted SIS Workstation software®
    .
  3. Delete the subfolder for the imported project in the AADvance projects folder on your hard drive.
  4. Open the project from
    AADvance-Trusted SIS Workstation software
    .