ControlLogix Change Detect with L6x Controllers
On L6x Change Detect assets, use RSLogix 5000 / Studio 5000 to configure the ControlLogix audit value with the “Correlation affected” option disabled. Leaving this option enabled could lead to unexpected behavior with the Change Detect schedule, including a repeating loop of Non-Consecutive Log Sequence.
See Knowledgebase Document ID: QA16985 - FactoryTalk AssetCentre: Non-Consecutive Log Sequence during Change Detect Schedule for more details.