Required security permissions

Users or groups must be granted with the appropriate security permissions to perform certain actions in the RecipePro+ editor. You can set the security permissions on the
Permissions
tab. To view the permissions, in the
Security Settings
dialog box, navigate to
FactoryTalk View SE
and expand it.
TIP:
To open the dialog box, in the
FactoryTalk View Studio
Explorer window, right-click the appropriate application or area and select
Security
.
Because security settings are inherited down the tree, choose the application or area at the highest possible level in the tree. For example, if you apply security settings at an application level, those settings apply to all of the areas within that application. If you apply security settings to a particular area, the settings apply to only that area and to other areas contained within that area.
To operate recipes in the RecipePro+ editor, users or groups must have at least the
RecipePro: Preview
permission. Otherwise, the recipes will not be visible in the editor.
TIP:
The
RecipePro: Preview
permission is specifically designed for
FactoryTalk ViewPoint
mobile users. If you want to restrict certain users to view and access the recipes on mobile devices, you must deny this permission for those users.
The following table shows additional security permissions required for certain actions.
To do this
You need these additional security permissions
Create a recipe
RecipePro: Create
Delete a recipe
RecipePro: Delete
Download a recipe
RecipePro: Download
Duplicate a recipe
RecipePro: Create
Edit a recipe
RecipePro: Edit
Modify a tag set
RecipePro: Edit
RecipePro: Modify TagSet
Import a recipe
RecipePro: Create
RecipePro: Edit
RecipePro: Modify TagSet
Rename a recipe
RecipePro: Edit
Upload a recipe
RecipePro: Edit
RecipePro: Upload
Upload and create a recipe
RecipePro: Create
RecipePro: Upload
RecipeProDownload command
RecipePro: Download
RecipeProUpload command
RecipePro: Edit
RecipePro: Upload
If you have secured HMI tags, the security codes are not validated at runtime. Users or groups that are not assigned the tags' security code are able to perform the download or upload operation.