FactoryTalk Batch Services Properties dialog—Secondary Server tab
In the
FactoryTalk Batch Services Properties
dialog, use the
Secondary Server
tab to configure secondary FactoryTalk® Batch
Server options.Secondary Server tab settings
The
Secondary Server
tab allows you to enable and set up
options for a secondary FactoryTalk Batch
Server to create a FactoryTalk Batch
Server pair that can resume or continue batch execution
on the other member of the pair.Setting | Description |
|---|---|
Enable secondary FactoryTalk Batch Server | Select this option to specify that the FactoryTalk Batch
Server must work in coordination with a secondary FactoryTalk Batch Server and enable secondary FactoryTalk Batch Server options throughout the
FactoryTalk Batch Services Properties
dialog.When you clear this checkbox, you also clear any value in the
Computer hosting the secondary FactoryTalk Batch
Server field. |
Computer hosting the secondary FactoryTalk Batch
Server | Browse to or enter the name of the host computer where the
secondary FactoryTalk Batch Server resides.The host computer name can only be used by one FactoryTalk Batch Server object in the FactoryTalk Directory —not any
other primary or secondary FactoryTalk Batch Server. If
you enter the same host computer name for more than one FactoryTalk Batch Server object in the FactoryTalk Directory , FactoryTalk Batch will use the configuration of the FactoryTalk Batch Server object associated with the
first instance it finds of the host computer name.
TIP:
Automated validation for
uniqueness of the
FactoryTalk Batch Server computer
assignment does not run during FactoryTalk Directory backup and restore of an
individual application, so you must verify the configuration to
avoid anomalous behavior. |
Batch creation
In the
Batch creation
area, you can configure how the
secondary FactoryTalk Batch
Server generates a unique ID for each batch at
batch creation, and the default batch name that the operator sees when adding a
batch.Setting | Description |
|---|---|
Create ID range | For the purpose of batch identification, the secondary FactoryTalk Batch Server generates a unique
CreateID for each batch at batch
creation. This Create ID range field controls the
range of IDs that the secondary FactoryTalk Batch
Server can use when generating a
CreateID . To make sure that all IDs
generated by a FactoryTalk Batch Server pair are
unique, you cannot select the same range for both the primary
FactoryTalk Batch Server and its secondary
server.
TIP:
The properties for the
Create ID range field for the primary
FactoryTalk Batch Server are in the
General tab. For more information,
see FactoryTalk Batch Services Properties dialog—General tab.To generate a new CreateID , the secondary
FactoryTalk Batch Server increments the last
CreateID by one (skipping any IDs
that exist in the eventdir.txt file). |
Default Batch ID | When adding a batch, one of the properties that the operator sees
in the FactoryTalk Batch View
Batch Creation page is the
Batch ID . This Default
Batch ID field defines the default value that
the operator initially sees in the Batch
ID property.The value in the Default Batch ID field
must meet the following requirements:
The default value for this required field is
BATCH_ID . |
Miscellaneous
The
Miscellaneous
area allows you to define options for hold
propagation and limits.When a batch executing in a secondary
FactoryTalk Batch
Server detects a
failure condition, the system may hold all or parts of a batch from propagating
through the recipe hierarchy. The selected Hold propagation
type identifies how much of the batch is commanded to hold in response to the
failure and how much continues to
run.Type | Description |
|---|---|
None | No hold. The entire batch continues running. |
Phase | Holds only the affected phase, allowing the balance of the
phase’s unit and all other units to continue running. |
Operation | Holds only the affected phase and the related operation, allowing
the balance of the operation’s unit and all other units to continue
running. |
Unit | Holds the phase and the related unit, and all other units
continue running. |
Batch | Holds the entire batch. This is the default value. |
Other settings in the
Miscellaneous
area allow you to define
options relating to limits.Setting | Description |
|---|---|
Maximum log file size (MB) | The secondary FactoryTalk Batch Server logs activities
to a log file (Batchsvr.log ). This required
field defines the maximum size (in megabytes) of the log file.
When the log file reaches maximum size, the log acts in a
circular manner, with new records overwriting the oldest
records.This field has a minimum integer value of 1 and a maximum integer
value of 1,024. The default value is 10
MB. |
Minimum disk space (MB) | This required field defines the minimum disk space (in MB) that
must be available before a batch can be added to the
BatchList . Adequate disk space helps
prevent data loss.This field has a minimum integer value of 1 and a maximum integer
value of 1,024. The default value is 1
MB. |
Maximum number of items to verify in parallel | From the FactoryTalk Batch Service Manager , you can issue a runtime command to the
secondary FactoryTalk Batch Server to verify tags in
the area model. Because attempting to verify all the tags
simultaneously can put a large load on the data servers
supporting those tags, and the customer could be running
batches, by default the command verifies one tag at a time.This required field allows you to increase the number of tags
that the command verifies at the same time, up to a maximum
integer value of 30. The default value is
1 . |
Minimum free virtual memory (MB) | This required field defines the minimum amount of virtual memory
(in MB) that must be available before the secondary FactoryTalk Batch Server will allow batch creation.
Adequate memory helps prevent FactoryTalk Batch Server
crashes.This field has a minimum integer value of 102 and a maximum
integer value of 3,840. The default value is
512 MB. |
OPC communications timeout
The
OPC communications timeout
area allows you to configure
the secondary FactoryTalk Batch
Server’s watchdog timer.Setting | Description |
|---|---|
Period (msec) | This required field defines the time interval (in milliseconds)
that the secondary FactoryTalk Batch Server uses to
check the quality of communication with FactoryTalk Live Data servers and
OPC data servers and to attempt to reconnect logic in the case
of lost data server connections.This field has a minimum integer value of 1,000 and a maximum
integer value of 60,000. The default value is
10,000 msec. |
Allowable failures | This required field defines how many consecutive failed watchdog
set or reset periods that the secondary FactoryTalk Batch Server permits before a FactoryTalk Live Data server or OPC data server connection status
is marked BAD and batches using that data server respond
according to their configured Hold
propagation type.This field has a minimum integer value of 2 and a maximum integer
value of 999,999,999. The default value is
5 . |