5034-AENTR and 5034-AENTRXT Adapters

5034-AENTR and 5034-AENTRXT Wiring Diagram
Technical Specifications - 5034-AENTR, 5034-AENTRXT
Attribute
5034-AENTR, 5034-AENTRXT
Number of I/O modules supported
32
A 5034-EXP or 5034-EXPXT is required when using more than 16 I/O modules.
Number of MB supported
16 for 18…30V DC
8 for 10…18V DC
MP voltage, nom
24V DC SELV
MP voltage range
10…30V DC SELV
MP current, nom
0.6 A @ 24V DC
MP current, max
850 mA @ 10V DC (8 MB)
800 mA @ 18V DC (16 MB)
500 mA @ 30V DC (16 MB)
Voltage and current ratings, MP inrush, max
6 A for 10 ms @ 24V DC SELV
Voltage and current ratings, SA
10…30V DC SELV, 10 A
Do not exceed 10 A current draw at the SA power RTB
Voltage and current ratings, backplane
16V DC, 300 mA max (8 MB)
16V DC, 600 mA max (16 MB)
SA power current at no load
2 mA
Power dissipation, max
3.6 W
Thermal dissipation, max
12.3 BTU/hr
Isolation voltage
250V (continuous), Basic Isolation, SA to backplane
250V (continuous), Basic Isolation, SA to MP
250V (continuous), Basic Isolation, Ethernet port to SA
60V (continuous), Basic Isolation, MP to backplane
60V (continuous), Basic Isolation, Ethernet port to MP
60V (continuous), Basic Isolation, Ethernet port to backplane
No isolation between Ethernet ports
Accessories shipped with adapter
5034-RTB6S – Push-in spring-type RTB
5034-ECR – End cap
RTB supported
5034-RTB6, 5034-RTB6S
Catalog numbers 5034-RTB6 and 5034-RTB6S are non-orderable.The adapter is shipped with only the 5034-RTB6S push-in spring-type RTB. If replacement or additional RTBs are required, order them separately using the following catalog numbers:
  • 5034-AENRTB-QTY5 for the 5034-RTB6 screw-type RTB.
  • 5034-AENRTBS-QTY5 for the 5034-RTB6S push-in spring-type RTB.
Each catalog number is supplied in packs of five RTBs.
Wiring category
(1)
2 - Power ports
2 - Ethernet ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
1 green/red network status indicator
2 green/red network connection status indicators
1 green module power status indicator
1 green SA power status indicator
Dimensions (HxWxD), approx
131.74 x 62.65 x 76 mm (5.18 x 2.46 x 2.99 in.)
Weight, approx
229 g (8.08 oz.) – 5034-AENTR
234 g (8.25 oz.) – 5034-AENTRXT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
NFC communication frequency
13.56 MHz passive type