Options on the Pens tab of the Trend Object Properties dialog box

The following table shows the options on the
Pens
tab of the
Trend Object Properties
dialog box.
Options
Descriptions
Pen Attributes
The
Pen Attributes
box is a spreadsheet where you can configure the individual attributes for each pen. The pen attributes define how the tag will be represented on the trend chart at runtime.
To see all of the available attributes, use the scroll bar at the bottom of the box.
Tag\Expr. name
Specifies a tag or expression whose value will be represented as a pen on the runtime chart.
The tag or expression is assigned on the
Connections
tab.
Color
Specifies the color of the pen line and the labels on the vertical axis.
Click in the column to change the color in the color palette.
Visible
Specifies whether the pen is visible or hidden on the trend. Click in the column to toggle the setting.
Width
Specifies the width of the pen line in pixels. The larger the size, the thicker the width.
If you select a width other than 1, you cannot change the line style setting.
Type
Specifies how trend lines are plotted on the chart. The available options are:
  • Analog
    . Plots pen lines using diagonals from one point to the next.
  • Digital
    . Plots pen lines using only horizontal and vertical lines between points.
  • Full width
    . Plots a tag's value as a horizontal line that extends across the full width of the chart. The tag moves up and down in the chart as the tag or expression changes.
Style
Specifies the style of the trend line: solid, dashed, dotted, and so on.
To use a line style other than a solid line, the line width must be set to 1.
Marker
Specifies the plot symbol for each data point.
On the
Display
tab, if you select
Show Only Markers
and do not connect data points, only the pens with assigned markers are shown on the trend chart.
Min / Max
Specifies the values represented by the bottom and the top of the chart. Tag values outside of the range determined by the minimum and maximum values might not appear on the chart.
To control the minimum and maximum range on the sides of the chart, use the
Min/Max Value
options on the
Y-Axis
tab.
Link Data
Select this check box to disable the
Min / Max
columns and use the assigned tag's minimum and maximum values. If the tag's minimum and maximum values are not available, the columns show question marks.
For digital tags, the minimum is 0 and the maximum is 1. For analog tags, specify the minimum and maximum values in the
Tags
editor.
Data Log Model
Specifies the data log model to use to supply historical data when the trend is first shown or when you scroll back in time. If you accept the default option,
None
, the trend shows only real time data.
Make sure you add the tags to the data log model.
Multiple Pen Edits
Specifies properties for multiple pens.
Clear Selections
Click this button to clear the selected edits in the
Multiple Pen Edits
spreadsheet.
Apply to Selected Pens
Click this button to apply the multiple pen edits to the pens selected in the
Pen Attributes
spreadsheet.