Command values
This table includes the command values:
COMMAND | DECIMAL | BINARY | HEX |
|---|---|---|---|
ABORT | 1 | 0000 0000 0000 0000 0001 | 0 0 0 0 1 |
HOLD | 2 | 0000 0000 0000 0000 0010 | 0 0 0 0 2 |
STOP | 4 | 0000 0000 0000 0000 0100 | 0 0 0 0 4 |
RESET | 8 | 0000 0000 0000 0000 1000 | 0 0 0 0 8 |
PAUSE | 16 | 0000 0000 0000 0001 0000 | 0 0 0 1 0 |
SEMIAUTO | 32 | 0000 0000 0000 0010 0000 | 0 0 0 2 0 |
DOWNLOAD | 64 | 0000 0000 0000 0100 0000 | 0 0 0 4 0 |
RESUME | 128 | 0000 0000 0000 1000 0000 | 0 0 0 8 0 |
RESTART | 256 | 0000 0000 0001 0000 0000 | 0 0 1 0 0 |
START | 512 | 0000 0000 0010 0000 0000 | 0 0 2 0 0 |
AUTO | 1024 | 0000 0000 0100 0000 0000 | 0 0 4 0 0 |
MANUAL | 2048 | 0000 0000 1000 0000 0000 | 0 0 8 0 0 |
STEP | 4096 | 0000 0001 0000 0000 0000 | 0 1 0 0 0 |
CLEARFAIL | 8192 | 0000 0010 0000 0000 0000 | 0 2 0 0 0 |
REMOVE | 16384 | 0000 0100 0000 0000 0000 | 0 4 0 0 0 |
BIND | 32768 | 0000 1000 0000 0000 0000 | 0 8 0 0 0 |
DISCONNECT | 65536 | 0001 0000 0000 0000 0000 | 1 0 0 0 0 |
CONNECT | 131072 | 0010 0000 0000 0000 0000 | 2 0 0 0 0 |
BINDPHASE | 262144 | 0100 0000 0000 0000 0000 | 4 0 0 0 0 |
TIMER-COMPLETE | 524288 | 0001 0000 0000 0000 0000 0000 | 1 0 0 0 0 0 |
TIMER-RESET | 1048576 | 1000 0000 0000 0000 0000 | 8 0 0 0 0 |
This table includes the masks and associated command:
MASK | COMMANDS |
0 | No Commands Enabled |
1 | ABORT |
5 | STOP ABORT |
7 | STOP HOLD ABORT |
32 | SEMIAUTO |
261 | RESTART STOP ABORT |
512 | START |
520 | START RESET |
560 | START SEMIAUTO PAUSE |
672 | START RESUME SEMIAUTO |
1024 | AUTO |
1056 | AUTO SEMIAUTO |
1536 | AUTO START |
1664 | AUTO START RESUME |
2080 | MANUAL SEMIAUTO |
2081 | MANUAL SEMIAUTO ABORT |
2085 | MANUAL SEMIAUTO STOP ABORT |
2087 | MANUAL SEMIAUTO STOP HOLD ABORT |
2341 | MANUAL RESTART SEMIAUTO STOP ABORT |
3072 | MANUAL AUTO |
3073 | MANUAL AUTO ABORT |
3077 | MANUAL AUTO STOP ABORT |
3079 | MANUAL AUTO STOP HOLD ABORT |
3207 | MANUAL AUTO RESUME STOP HOLD ABORT |
3333 | MANUAL AUTO RESTART STOP ABORT |
4096 | ASC |
5152 | ASC AUTO SEMIAUTO |
8192 | CLEARFAIL |
10272 | CLEARFAIL MANUAL SEMIAUTO |
10273 | CLEARFAIL MANUAL SEMIAUTO ABORT |
10277 | CLEARFAIL MANUAL SEMIAUTO STOP ABORT |
10279 | CLEARFAIL MANUAL SEMIAUTO STOP HOLD ABORT |
11264 | CLEARFAIL MANUAL AUTO |
11265 | CLEARFAIL MANUAL AUTO ABORT |
11269 | CLEARFAIL MANUAL AUTO STOP ABORT |
11271 | CLEARFAIL MANUAL AUTO STOP HOLD ABORT |
16392 | REMOVE RESET |
16928 | REMOVE START SEMIAUTO |
18464 | REMOVE MANUAL SEMIAUTO COMMENT |
18472 | REMOVE MANUAL SEMIAUTO RESET |
18976 | REMOVE MANUAL START SEMIAUTO |
19464 | REMOVE MANUAL AUTO RESET |
19968 | REMOVE MANUAL AUTO START |
24608 | REMOVE CLEARFAIL SEMIAUTO |
26656 | REMOVE CLEARFAIL MANUAL SEMIAUTO |
26664 | REMOVE CLEARFAIL MANUAL SEMIAUTO RESET |
27648 | REMOVE CLEARFAIL MANUAL AUTO |
27656 | REMOVE CLEARFAIL MANUAL AUTO RESET |
32768 | BIND |
32769 | BIND ABORT |
32773 | BIND STOP ABORT |
32775 | BIND STOP HOLD ABORT |
32800 | BIND SEMIAUTO |
33029 | BIND RESTART STOP ABORT |
33280 | BIND START |
33288 | BIND START RESET |
33328 | BIND START SEMIAUTO PAUSE |
33440 | BIND START RESUME SEMIAUTO |
33792 | BIND AUTO |
33824 | BIND AUTO SEMIAUTO |
34304 | BIND AUTO START |
34432 | BIND AUTO START RESUME |
34848 | BIND MANUAL SEMIAUTO |
34849 | BIND MANUAL SEMIAUTO ABORT |
34853 | BIND MANUAL SEMIAUTO STOP ABORT |
34855 | BIND MANUAL SEMIAUTO STOP HOLD ABORT |
35109 | BIND MANUAL RESTART SEMIAUTO STOP ABORT |
35840 | BIND MANUAL AUTO |
35841 | BIND MANUAL AUTO ABORT |
35845 | BIND MANUAL AUTO STOP ABORT |
35847 | BIND MANUAL AUTO STOP HOLD ABORT |
35975 | BIND MANUAL AUTO RESUME STOP HOLD ABORT |
36101 | BIND MANUAL AUTO RESTART STOP ABORT |
36864 | BIND ASC |
37920 | BIND ASC AUTO SEMIAUTO |
40960 | BIND CLEARFAIL |
43040 | BIND CLEARFAIL MANUAL SEMIAUTO |
43041 | BIND CLEARFAIL MANUAL SEMIAUTO ABORT |
43045 | BIND CLEARFAIL MANUAL SEMIAUTO STOP ABORT |
43047 | BIND CLEARFAIL MANUAL SEMIAUTO STOP HOLD ABORT |
44032 | BIND CLEARFAIL MANUAL AUTO |
44033 | BIND CLEARFAIL MANUAL AUTO ABORT |
44037 | BIND CLEARFAIL MANUAL AUTO STOP ABORT |
44039 | BIND CLEARFAIL MANUAL AUTO STOP HOLD ABORT |
49160 | BIND REMOVE RESET |
49696 | BIND REMOVE START SEMIAUTO |
51240 | BIND REMOVE MANUAL SEMIAUTO RESET |
51744 | BIND REMOVE MANUAL START SEMIAUTO |
52232 | BIND REMOVE MANUAL AUTO RESET |
52736 | BIND REMOVE MANUAL AUTO START |
57376 | BIND REMOVE CLEARFAIL SEMIAUTO |
59424 | BIND REMOVE CLEARFAIL MANUAL SEMIAUTO |
59432 | BIND REMOVE CLEARFAIL MANUAL SEMIAUTO RESET |
60416 | BIND REMOVE CLEARFAIL MANUAL AUTO |
60424 | BIND REMOVE CLEARFAIL MANUAL AUTO RESET |
65536 | DISCONNECT |
65568 | DISCONNECT SEMIAUTO |
65569 | DISCONNECT SEMIAUTO ABORT |
65573 | DISCONNECT SEMIAUTO STOP ABORT |
65575 | DISCONNECT SEMIAUTO STOP HOLD ABORT |
65584 | DISCONNECT SEMIAUTO PAUSE |
65585 | DISCONNECT SEMIAUTO PAUSE ABORT |
65589 | DISCONNECT SEMIAUTO PAUSE STOP ABORT |
65591 | DISCONNECT SEMIAUTO PAUSE STOP HOLD ABORT |
65696 | DISCONNECT RESUME SEMIAUTO |
65697 | DISCONNECT RESUME SEMIAUTO ABORT |
65701 | DISCONNECT RESUME SEMIAUTO STOP ABORT |
65703 | DISCONNECT RESUME SEMIAUTO STOP HOLD ABORT |
65829 | DISCONNECT RESTART SEMIAUTO STOP ABORT |
65845 | DISCONNECT RESTART SEMIAUTO PAUSE STOP ABORT |
65957 | DISCONNECT RESTART RESUME SEMIAUTO STOP ABORT |
66104 | DISCONNECT START SEMIAUTO PAUSE RESET |
66216 | DISCONNECT START RESUME SEMIAUTO RESET |
66560 | DISCONNECT AUTO |
66561 | DISCONNECT AUTO ABORT |
66565 | DISCONNECT AUTO STOP ABORT |
66567 | DISCONNECT AUTO STOP HOLD ABORT |
66688 | DISCONNECT AUTO RESUME |
66689 | DISCONNECT AUTO RESUME ABORT |
66693 | DISCONNECT AUTO RESUME STOP ABORT |
66695 | DISCONNECT AUTO RESUME STOP HOLD ABORT |
66821 | DISCONNECT AUTO RESTART STOP ABORT |
66949 | DISCONNECT AUTO RESTART RESUME STOP ABORT |
67072 | DISCONNECT AUTO START |
67080 | DISCONNECT AUTO START RESET |
67208 | DISCONNECT AUTO START RESUME RESET |
73728 | DISCONNECT CLEARFAIL |
73729 | DISCONNECT CLEARFAIL ABORT |
73733 | DISCONNECT CLEARFAIL STOP ABORT |
73735 | DISCONNECT CLEARFAIL STOP HOLD ABORT |
73736 | DISCONNECT CLEARFAIL RESET |
73760 | DISCONNECT CLEARFAIL SEMIAUTO |
73761 | DISCONNECT CLEARFAIL SEMIAUTO ABORT |
73765 | DISCONNECT CLEARFAIL SEMIAUTO STOP ABORT |
73767 | DISCONNECT CLEARFAIL SEMIAUTO STOP HOLD ABORT |
74752 | DISCONNECT CLEARFAIL AUTO |
74753 | DISCONNECT CLEARFAIL AUTO ABORT |
74757 | DISCONNECT CLEARFAIL AUTO STOP ABORT |
74759 | DISCONNECT CLEARFAIL AUTO STOP HOLD ABORT |
74880 | DISCONNECT CLEARFAIL AUTO RESUME |
74881 | DISCONNECT CLEARFAIL AUTO RESUME ABORT |
74885 | DISCONNECT CLEARFAIL AUTO RESUME STOP ABORT |
74887 | DISCONNECT CLEARFAIL AUTO RESUME STOP HOLD ABORT |
81928 | DISCONNECT REMOVE RESET |
81960 | DISCONNECT REMOVE SEMIAUTO RESET |
82464 | DISCONNECT REMOVE START SEMIAUTO |
82952 | DISCONNECT REMOVE AUTO RESET |
83080 | DISCONNECT REMOVE AUTO RESUME RESET |
90120 | DISCONNECT REMOVE CLEARFAIL RESET |
90144 | DISCONNECT REMOVE CLEARFAIL SEMIAUTO |
98304 | DISCONNECT BIND |
98336 | DISCONNECT BIND SEMIAUTO |
98337 | DISCONNECT BIND SEMIAUTO ABORT |
98341 | DISCONNECT BIND SEMIAUTO STOP ABORT |
98343 | DISCONNECT BIND SEMIAUTO STOP HOLD ABORT |
98352 | DISCONNECT BIND SEMIAUTO PAUSE |
98353 | DISCONNECT BIND SEMIAUTO PAUSE ABORT |
98357 | DISCONNECT BIND SEMIAUTO PAUSE STOP ABORT |
98359 | DISCONNECT BIND SEMIAUTO PAUSE STOP HOLD ABORT |
98464 | DISCONNECT BIND RESUME SEMIAUTO |
98465 | DISCONNECT BIND RESUME SEMIAUTO ABORT |
98469 | DISCONNECT BIND RESUME SEMIAUTO STOP ABORT |
98471 | DISCONNECT BIND RESUME SEMIAUTO STOP HOLD ABORT |
98597 | DISCONNECT BIND RESTART SEMIAUTO STOP ABORT |
98613 | DISCONNECT BIND RESTART SEMIAUTO PAUSE STOP ABORT |
98725 | DISCONNECT BIND RESTART RESUME SEMIAUTO STOP ABORT |
98872 | DISCONNECT BIND START SEMIAUTO PAUSE RESET |
98984 | DISCONNECT BIND START RESUME SEMIAUTO RESET |
99328 | DISCONNECT BIND AUTO |
99329 | DISCONNECT BIND AUTO ABORT |
99333 | DISCONNECT BIND AUTO STOP ABORT |
99335 | DISCONNECT BIND AUTO STOP HOLD ABORT |
99456 | DISCONNECT BIND AUTO RESUME |
99457 | DISCONNECT BIND AUTO RESUME ABORT |
99461 | DISCONNECT BIND AUTO RESUME STOP ABORT |
99463 | DISCONNECT BIND AUTO RESUME STOP HOLD ABORT |
99589 | DISCONNECT BIND AUTO RESTART STOP ABORT |
99717 | DISCONNECT BIND AUTO RESTART RESUME STOP ABORT |
99840 | DISCONNECT BIND AUTO START |
99848 | DISCONNECT BIND AUTO START RESET |
99976 | DISCONNECT BIND AUTO START RESUME RESET |
106496 | DISCONNECT BIND CLEARFAIL |
106497 | DISCONNECT BIND CLEARFAIL ABORT |
106501 | DISCONNECT BIND CLEARFAIL STOP ABORT |
106503 | DISCONNECT BIND CLEARFAIL STOP HOLD ABORT |
106504 | DISCONNECT BIND CLEARFAIL RESET |
106528 | DISCONNECT BIND CLEARFAIL SEMIAUTO |
106529 | DISCONNECT BIND CLEARFAIL SEMIAUTO ABORT |
106533 | DISCONNECT BIND CLEARFAIL SEMIAUTO STOP ABORT |
106535 | DISCONNECT BIND CLEARFAIL SEMIAUTO STOP HOLD ABORT |
107520 | DISCONNECT BIND CLEARFAIL AUTO |
107521 | DISCONNECT BIND CLEARFAIL AUTO ABORT |
107525 | DISCONNECT BIND CLEARFAIL AUTO STOP ABORT |
107527 | DISCONNECT BIND CLEARFAIL AUTO STOP HOLD ABORT |
107648 | DISCONNECT BIND CLEARFAIL AUTO RESUME |
107649 | DISCONNECT BIND CLEARFAIL AUTO RESUME ABORT |
107653 | DISCONNECT BIND CLEARFAIL AUTO RESUME STOP ABORT |
107655 | DISCONNECT BIND CLEARFAIL AUTO RESUME STOP HOLD ABORT |
114696 | DISCONNECT BIND REMOVE RESET |
114728 | DISCONNECT BIND REMOVE SEMIAUTO RESET |
115232 | DISCONNECT BIND REMOVE START SEMIAUTO |
115720 | DISCONNECT BIND REMOVE AUTO RESET |
115848 | DISCONNECT BIND REMOVE AUTO RESUME RESET |
122888 | DISCONNECT BIND REMOVE CLEARFAIL RESET |
122912 | DISCONNECT BIND REMOVE CLEARFAIL SEMIAUTO |