Troubleshoot mismatched configurations when performing Siemens TIA Portal Disaster Recovery tasks
When configuring the asset properties for Siemens S7 Controller (TIA Portal), you must use the matched file version in backup data, TIA Portal versions, and physical controllers to make sure the Disaster Recovery schedules run successfully. The following table shows the correct configuration scenario.
Scenario | Disaster Recovery Behavior |
|---|---|
In asset properties: Select a .ZAP16 file in Backup Data Browser .Set TIA Portal Version to TIA Portal V16 .Specify the address of a physical controller running v16 firmware. | Backup task behavior: Task succeeds. |
Backup and Compare task behavior: Task succeeds. |
Mismatched file versions in backup data, TIA Portal versions, and physical controllers may result in task failures with different error messages. The following table shows several mismatched scenarios when running Siemens TIA Portal disaster recovery tasks.
Scenario | Disaster Recovery Behavior |
|---|---|
In asset properties: Select a .ZAP16 file in Backup Data Browser .Set TIA Portal Version to TIA Portal V16 .Specify the address of the physical controller running v18 firmware. | Backup task behavior: The task failed with the error "TIA Portal error occurred during task execution (0x0019)" recorded in the Event Log. |
Backup and Compare task behavior: The task failed with the error "TIA Portal error occurred during task execution (0x0019)" recorded in the Event Log. | |
In asset properties: Select a .ZAP16 file in Backup Data Browser .Set TIA Portal Version to TIA Portal V18 .Specify the address of the physical controller running v16 firmware. | Backup task behavior: The task failed with the error "TIA Portal disaster recovery task failed due to TIA Portal Version and Backup Data mismatch" recorded in the Event Log. |
Backup and Compare task behavior: The task failed with the error "TIA Portal disaster recovery task failed due to TIA Portal Version and Backup Data mismatch" recorded in the Event Log. | |
In asset properties: Select a .ZAP18 file in Backup Data Browser . Set TIA Portal Version to TIA Portal V16 .Specify the address of the physical controller running v16 firmware. | Backup task behavior: The task failed with the error "TIA Portal disaster recovery task failed due to TIA Portal Version and Backup Data mismatch" recorded in the Event Log. |
Backup and Compare task behavior: The task failed with the error "TIA Portal disaster recovery task failed due to TIA Portal Version and Backup Data mismatch" recorded in the Event Log. |
Provide Feedback