:6Ah error in the DDE/OPC Communications Event Log

Possible solution
When a
:6Ah
error is generated in the DDE/OPC Communications Event Log (for example,
AB_ETH-1\130.130.130.130: S:42 : 09/26/03 - 13:47:28 : 6Ah
), append an option (
:V4
) to the EtherNet/IP address while configuring an Ethernet driver (AB-ETH) that specifies the driver always uses the legacy CSPV4 protocol for SLC 500 processors. For example,
130.130.130.130:V4
.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.