Configure a dual channel 1784-PKTX(D) driver (Windows Server 2012)
When you are running
FactoryTalk Linx
and RSLinx Classic
on the same computer (Windows Server 2012), and your FactoryTalk Linx
or RSLinx Classic
configuration consists of a dual-channel 1784-PKTX(D) driver, you configure the driver for both FactoryTalk Linx
and RSLinx Classic
.
TIP:
This applies only to the dual-channel 1784-PKTX(D) driver. The single-channel 1784-PKTX driver can be configured in only one
RSLinx
product at a time.To configure the 1784-PKTX(D) driver for
FactoryTalk Linx
andRSLinx Classic
- If you do not already have a 1784-PKTX(D) driver inFactoryTalk Linx, then right-clickFactoryTalk Linx, clickAdd Driver, and select a 1784-PKTX(D) driver from the list.TheorDH+Driver PropertiesDH485 Driver Propertiesdialog box opens.
- Verify the information in the dialog box fields is correct, and clickOK.
- StartRSLinx Classic, and clickCommunications > Configure Drivers.TheConfigure Driversdialog box opens.
- From theAvailable Driver Typeslist, click the 1784-PKTX(D) driver,and then clickAdd New.
- In theAdd Newdialog box, enter a driver name or use the default name. ClickRSLinx ClassicDriverOK.TheConfigure 1784-PKTX/PKTXDdialog box opens.
- Select the driver type from theValuelist, and clickOK.