Unit Bind Signature request
Overview
If a Bind Command Verification policy is configured in the area model and it is
associated with a Signature Template, then a
Unit Bind
Signature
request is generated when a user attempts to bind a Unit
to a step.Modifications made to support FactoryTalk Batch electronic signatures
The following is an explanation of the modifications made to support
FactoryTalk® Batch
electronic signature:Bind Execute | |
|---|---|
Batch Server | When the FactoryTalk Batch Server receives a legal Bind
execute, the Area Model configuration is checked to determine if
a confirmation signature is required for the Bind request. If
one is required, then a Signature Request is generated using the
specified Signature Template and the Bind action is queued
pending Signature completion. |
Response | An ActionID is returned by the Execute used to locate the
generated signature. |
Completion | When all Signature Signoffs associated with a Bind Execute Action
are completed, then the Unit Requirement targeted by the Bind
Execute Action is bound to the specified Unit if the bind action
is still legal. |
Cancellation | When any Signature generated by a Bind Execute Action is
cancelled, then the Bind Action is terminated and its associated
incomplete Signature Requests are System Cancelled. |
Overlap | If a Bind Execute is received while an earlier Bind Execute
Action is pending for the same target Unit Requirement, then the
new Bind Execute fails. The failed execute’s response item is
populated with an appropriate response string. For purposes of
determining the legality of overlapping executes, Command, Step,
Remove, and BindPhase Executes are treated as being Bind
Executes. This means, for example, that if a Step Execute Action
is pending Signature completion on a procedure, then a Bind
Execute to the same procedure fails because of the overlap with
the Step execute. |
Automatic Cancellation | If any step associated with the Unit Requirement being targeted
by a queued Bind Execute Action becomes an active recipe
element, then the Bind Execute Action is terminated and its
associated incomplete Signature Requests are System Cancelled.
This happens because the Bind action is not legal for a Unit
Requirement associated with any active steps. |
Warm Restart, Warm All Restart, or Hot Restart | Signature Requests generated in response to a Bind Execute Action
are restored in the event of a FactoryTalk Batch Server Warm Restart, Warm All Restart, or Hot Restart. |
Provide Feedback