Unit Bind Prompt Acknowledge Signature request
Overview
If a Bind Ack Command Verification policy is configured in the area model and it is
associated with a Signature Template, then a
Unit Bind Prompt Acknowledge
Signature
request is generated when binding a Unit to a step after a
prompt has been generated or prompting binds a Unit to a step.Modifications made to support FactoryTalk Batch electronic signatures
The following is an explanation of the modifications made to support
FactoryTalk® Batch
electronic signatures:Unit Bind Execute | |
|---|---|
Batch Server | When the FactoryTalk Batch Server receives a legal Ack
execute in response to a Unit Bind UnacknowledgedEvent, it may
queue the bind selection delivery pending a Signature Request if
such behavior is configured in the area model. |
Response | An ActionID is returned by the Execute used to locate the
generated signature. |
Completion | When all Signature Signoffs generated by an Ack received in
response to a Unit Bind UnacknowledgedEvent are completed, then
the Unit Requirement binds to the Ack execute response Unit
specified if the bind action is still legal. |
Cancellation | When any Signature generated by a Unit Bind Ack execute is
cancelled, then the Unit Bind Ack Action is terminated and its
associated incomplete Signature Requests are System
Cancelled. |
Overlap | If a Unit Bind Ack execute response to a Unit Bind Prompt is
received while there are existing incomplete Signature Requests
generated by a prior Unit Bind Ack Action targeting the same
prompt, or the Batch has a Remove Action pending, then the new
execute fails. The failed execute’s response item is populated
with an appropriate error message string. |
Automatic Cancellation | If the batch system cancels an UnacknowledgedEvent targeted by a
Unit Bind Ack Action, then the queued Execute Action is
terminated and all incomplete Signature Requests associated with
the Action are System Cancelled. |
Warm Restart, Warm All Restart, or Hot Restart | Signature Requests generated in response to a Unit Bind Ack
Execute Action are System Cancelled in the event of a FactoryTalk Batch Server Warm Restart, Warm All
Restart, or Hot Restart. |