Tech Access Register Map
The Tech Access Register map contains parameters used developers for testing the PQconnect board and filter or left for future implementation and is only usable for TCI, LLC.
Note:
All parameters with an asterisk (*) in the description will require the Tech level access codes parameter key A: 0x007D (125) and parameter key B: 0xEA6E (60014). All parameters are enabled for communication to EtherNet/IP unless explicitly stated otherwise in the Notes Column of the Table.
Table
15
: Tech Access Feedback and Setpoint Parameters Register Map
Parameter Name (EtherNet/IP Name) | Instance ID | Description | Type | Default & Ranges | Notes |
SYS_PEEK_0 (DiagVal0) | 304 | Diagnostic peek value 0 | R | Default:0 | A diagnostic Feedback variable used by Production and Engineering for Testing and Field Support. |
SYS_PEEK_1 (DiagVal1) | 305 | Diagnostic peek value 1 | R | Default:0 | |
SYS_PEEK_2 (DiagVal2) | 306 | Diagnostic peek value 2 | R | Default:0 | |
SYS_PEEK_3 (DiagVal3) | 307 | Diagnostic peek value 3 | R | Default:0 | |
TEST_VOLTAGE (TestVoltage) | 13 | Unit test voltage, (10 = 1.0 Volts) | R/W | Default:0 Range:0 to 6900 | Factory Used Parameter. Used to check if Filter was configured with the correct test Voltage. |
TEST_FREQUENCY (TestFreq) | 14 | Unit test frequency, (Hz) | R/W | Default:0 Range:0 to 60 | Factory Used Parameter. Used to check if Filter was configured with the correct test frequency. |
SYS_POKE_0 (Poke0) | 166 | Diagnostic poke variable 0 | R/W | Default:0 Range:-32768 to 32767 | |
SYS_POKE_1 (Poke1) | 167 | Diagnostic poke variable 1 | R/W | Default:0 Range:-32768 to 32767 | |
SYS_POKE_2 (Poke2) | 168 | Diagnostic poke variable 2 | R/W | Default:0 Range:-32768 to 32767 | |
SYS_POKE_3 (Poke3) | 169 | Diagnostic poke variable 3 | R/W | Default:0 Range:-32768 to 32767 | |
SYS_PEEK_ADDR_0 (PeekAddr0) | 170 | Diagnostic peek address 0 | R/W | Default:0 Range:0 to 65535 | |
SYS_PEEK_ADDR_1 (PeekAddr1) | 171 | Diagnostic peek address 1 | R/W | Default:0 Range:0 to 65535 | |
SYS_PEEK_ADDR_2 (PeekAddr2) | 172 | Diagnostic peek address 2 | R/W | Default:0 Range:0 to 65535 | |
SYS_PEEK_ADDR_3 (PeekAddr3) | 173 | Diagnostic peek address 3 | R/W | Default:0 Range:0 to 65535 | |
BGM_PASSKEY_A_EIP (DiagFb1) | 313 | Diagnostic Feedback Parameter 1 | R | Default:0 | Ethernet Enabled but Mapped to Modbus Instance: BGM_PASSKEY_A Read only Value of BGM Password - High Bytes |
BGM_PASSKEY_B_EI (DiagFb2) | 314 | Diagnostic Feedback Parameter 2 | R | Default:0 | "Ethernet Enabled but Mapped to Modbus Instance: BGM_PASSKEY_B Read only Value of BGM Password - Low Bytes |
DIAGONSTIC_FEEDBACK_3 (DiagFb3) | 315 | Diagnostic Feedback Parameter 3 | R | Default:0 | EtherNet Only: Reserved Does not exist in Database. |
DIAGONSTIC_FEEDBACK_4 (DiagFb4) | 316 | Diagnostic Feedback Parameter 4 | R | Default:0 | |
SYS_COM_ACTIVE (DiagFb5) | 317 | Diagnostic Feedback Parameter 5 | R | Default:0 | System Communication Status, bit 0 = Modbus RTU active, bit 1 = Bluetooth active, bit 2 = EtherNet/IP active |
SYS_CNT_MIN_OFF_TIMER_EIP (DiagFb6) | 318 | Diagnostic Feedback Parameter 6 | R | Default:0 | Ethernet Enabled but Mapped to Modbus Instance: SYS_CNT_MIN_OFF_TIMER Displays count down time for contactor re-closures. Once this timer expires contactor will change the contactor state to close. Default: 60 seconds Range: 30 to 300 seconds |
PARAM_ACCESS_LEVEL_EIP (DiagFb7) | 319 | Diagnostic Feedback Parameter 7 | R | Default:0 | Ethernet Enabled but Mapped to Modbus Instance: PARAM_ACCESS_LEVEL_RO Determines the Level of parameter access to read and/or change parameter inputs. 0 = Base access 1 = Tech access 2 = Factory access |
DIAGONSTIC_FEEDBACK_9 (DiagFb9) | 320 | Diagnostic Feedback Parameter 7 | R | Default:0 | EtherNet Only: Reserved Does not exist in Database |
DIAGONSTIC_FEEDBACK_10 (DiagFb10) | 321 | Diagnostic Feedback Parameter 10 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_11 (DiagFb11) | 322 | Diagnostic Feedback Parameter 10 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_12 (DiagFb12) | 323 | Diagnostic Feedback Parameter 12 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_13 (DiagFb13) | 324 | Diagnostic Feedback Parameter 13 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_14 (DiagFb14) | 325 | Diagnostic Feedback Parameter 14 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_15 (DiagFb15) | 326 | Diagnostic Feedback Parameter 15 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_16 (DiagFb16) | 327 | Diagnostic Feedback Parameter 16 | R | Default:0 | |
DIAGONSTIC_FEEDBACK_8 (DiagFb8) | 328 | Diagnostic Feedback Parameter 8 | R | Default:0 | |
DIAG_SETPOINT_1 (DiagSP1) | 190 | Diagnostic Setpoint Parameter 1 | R/W | Default:0 Range:0 to 0 | EtherNet Only: Reserved Does not exist in Database. |
DIAG_SETPOINT_2 (DiagSP2) | 191 | Diagnostic Setpoint Parameter 2 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_3 (DiagSP3) | 192 | Diagnostic Setpoint Parameter 3 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_4 (DiagSP4) | 193 | Diagnostic Setpoint Parameter 4 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_5 (DiagSP5) | 194 | Diagnostic Setpoint Parameter 5 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_6 (DiagSP6) | 195 | Diagnostic Setpoint Parameter 6 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_7 (DiagSP7) | 196 | Diagnostic Setpoint Parameter 7 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_8 (PROC_DATA_CMD_EN) | 197 | Diagnostic Setpoint Parameter 8 | R/W | Default:0 Range:0 to 1 | Enables and Disables Implicit Setpoint Writes. Only used for Passive Filters with EtherNet/IP Connectivity. 0 = Implicit IO Writes Disabled 1 = Implicit IO Writes Enabled |
DIAG_SETPOINT_9 (DiagSP9) | 198 | Diagnostic Setpoint Parameter 9 | R/W | Default:0 Range:0 to 0 | EtherNet Only: Reserved Does not exist in Database. |
DIAG_SETPOINT_10 (DiagSP10) | 199 | Diagnostic Setpoint Parameter 10 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_11 (DiagSP11) | 200 | Diagnostic Setpoint Parameter 11 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_12 (DiagSP12) | 201 | Diagnostic Setpoint Parameter 12 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_13 (DiagSP13) | 202 | Diagnostic Setpoint Parameter 13 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_14 (DiagSP14) | 203 | Diagnostic Setpoint Parameter 14 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_15 (DiagSP15) | 204 | Diagnostic Setpoint Parameter 15 | R/W | Default:0 Range:0 to 0 | |
DIAG_SETPOINT_16 (DiagSP16) | 205 | Diagnostic Setpoint Parameter 16 | R/W | Default:0 Range:0 to 0 | |
V_OUT_FUND_HZ (FFund) | 270 | Load output voltage fundamental frequency, (Hz) | R | Default:0 | |
V_IN_CARRIER_HZ (FCarrier) | 271 | Estimated input voltage carrier frequency, (Hz) | R | Default:0 | |
FUND_TRACKING_MODE (FundFreqTrackMode) | 111 | Fundamental frequency tracking mode | R/W | Default:0 Range:0 to 0 | |
FUND_TRACKING_FILTER _GAIN (FundFreqFiltGain) | 112 | Fundamental frequency reference filter gain | R/W | Default:0 Range:0 to 0 |