Status Register Map

This register map contains Filter and Line Status parameters used by the passive filter. Please reference the Filter Status Table in the IOM if needed.
Note:
All parameters with an asterisk (*) in the description will require the Tech level access codes parameter key A: 0x007D (125) and parameter key B: 0xEA6E (60014). All parameters are enabled for communication to EtherNet/IP unless explicitly stated otherwise in the Notes Column of the Table.
Table
1
:
Status Feedback and Setpoint Parameters Register Map
Parameter Name
(EtherNet/IP Name)
Instance ID
Description
Type
Default & Ranges
Notes
USER_STATE
(UserState)
206
User State
R
Default:0
User State Parameter
00 = INIT_START
01 = INIT_DELAY
02 = INIT_E2_CHIP
03 = INIT_FLASH_TEST
04 = WRITE_FLASH_TEST
05 = SETUP_FLASH
06 = SETUP_NON_CAL_FLASH
07 = SAVE_CURRENT_VALUES
08 = STAMP_EE
09 = INIT_FROM_DEFAULTS
10 = INIT_FROM_FLASH
11 = EXECUTE_PARAM_FUNCTIONS
12 = PARAM_INIT_FINISH
13 = RESTORE_DEFAULTS
14 = RESTORE_NON_CAL_DEFAULT
15 = INIT_SAVE_CURRENT_VALUES
16 = REBOOT
17 = SETUP_UNIT_CAL_FLASH
18 = RESTORE_UNIT_CAL_DEFAULT
19 = UPDATE_EEPROM
20 = UNPROTECT_EEPROM
21 = PROTECT_EEPROM
CNT_CLOSED
(CntClosed)
272
Filter tuned circuit contactor closed
R
Default:0
Indicates the status of the Filters tuned circuit contactor.
0 = Contactor Closed
1 = Contactor Open
SYS_POWER_ON
(PowerOn)
273
Filter powered on
R
Default:0
Indicates if the filter has input power available
0 = Power Off
1 = Power On
SYS_STATUS_OK
(StatusOK)
274
Filter status OK
R
Default:0
Indicates filters status
0 = Filter is operating
1 = Filter has indicated status warning
SYS_AT_CAPACITY
(AtCapacity)
275
Filter at maximum capacity
R
Default:0
Indicates if the filter is running at its maximum current capacity
0 = Nominal
1 = At Capacity
STATUS_FILTER_A
(FilterStatusActiveA)
279
Filter status detection active A bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
STATUS_FILTER_B
(FilterStatusActiveB)
280
Filter status detection active B bit mask
R
Default:0
STATUS_LINE
(LineStatusActive)
281
Line status detection active bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
STATUS_FILTER_LOAD (LoadStatusActive)
282
Filter load status detection bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
STATUS_FILTER_A_ENABLE_RO
(FilterStatusEnabledA)
283
Filter status A detection enable bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
STATUS_FILTER_B_ENABLE_RO
(FilterStatusEnabledB)
284
Filter status B detection enable bit mask
R
Default:0
STATUS_LINE_ENABLE_RO
(LineStatusEnabled)
285
Line status detection enable bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
STATUS_FILTER_LOAD_ENABLE_RO
(LoadStatusEnabled)
286
Filter load status detection enable bit mask
R
Default:0
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal Range: 0 to 65535
PARAM_STATE
(ParamState)
287
Parameter state
R
Default:0
Indicates the present state of the parameter state machine.
00 = INIT_START
01 = INIT_DELAY
02 = INIT_E2_CHIP
03 = INIT_FLASH_TEST
04 = WRITE_FLASH_TEST
05 = SETUP_FLASH
06 = SETUP_NON_CAL_FLASH
07 = SAVE_CURRENT_VALUES
08 = STAMP_EE
09 = INIT_FROM_DEFAULTS
10 = INIT_FROM_FLASH
11 = EXECUTE_PARAM_FUNCTIONS
12 = PARAM_INIT_FINISH
13 = RESTORE_DEFAULTS
14 = RESTORE_NON_CAL_DEFAULTS
15 = INIT_SAVE_CURRENT_VALUES
16 = REBOOT
17 = SETUP_UNIT_CAL_FLASH
18 = RESTORE_UNIT_CAL_DEFAULTS
19 = UPDATE_EEPROM
20 = UNPROTECT_EEPROM
21 = PROTECT_EEPROM
SYS_STATE
(SysState)
288
System state
R
Default:0
Indicates the present state of the system state machine (Read Only)
00 = Initialization State Machine
01 = Initialization Parameters
02 = Power on Delay
03 = Unit State Configuration Check
04 = Reset
05 = Force Open Contactor
06 = Force Close Contactor
07 = Auto Load Open
08 = Auto Load Close
09 = Auto kVAR Close
10 = Auto kVAR Open
11 = External Open
12 = External Close
13 = No Contactor
14 = Contactor Closed Inhibited
15 = Calibrate offsets
16 = Calibrate Magnitude
17 = No Communication
18 = Communication configuration
19 = PCB Calibration Check
20 = Unit Calibration Check
21 = Pre-Calibration Check
22 = Unit in Contactor Debug Close
CNT_STATUS
(CntStatus)
289
Contactor command status
R
Default:0
Indicates the present contactor status command,
00 = Init State at Startup
01 = Force Close Condition
02 = Force Open Condition
03 = Auto Load Open Condition
04 = Auto kVAR Open Condition
05 = External Open Condition
06 = No Contactor Condition
07 = Contactor Open
08 = Contactor Param Inhibit
09 = Contactor Power On Inhibit
10 = Contactor Calibrate Inhibit
11 = Contactor Min Reclose
12 = Contactor Close Delay
13 = Contactor Auto Reclose Delay
14 = Contactor Auto Reclose Limit
15 = Contactor Config Inhibit
RELAY_INPUT_STATUS
(RelayInputStatus)
290
Digital relay input status
R
Default:0
Filter Relay Input Status,
0b00 = Relay 1 (Temp Okay), Relay 2 (Temp Okay)
0b01 = Relay 1 (Temp Hot), Relay 2 (Temp Okay)
0b10 = Relay 1 (Temp Okay), Relay 2 (Temp Hot)
0b11 = Relay 1 (Temp Hot), Relay 2 (Temp Hot)
FIELDBUS_STATUS_A
(FBStatusA)
294
Field Bus communication status A Register
R
Default:0
Ethernet Module Status Register A Notifies the User of the status of the EtherNet/IP Module.
FIELDBUS_STATUS_B
(FBStatusB)
295
Field Bus communication status B Register
R
Default:0
Ethernet Module Status Register B Notifies the User of the status of the EtherNet/IP Module.
SYS_NULL_STAT
(PCBCalStatus)
296
Factory PCB calibration status
R
Default:0
System PCB Calibration Status
0 = Not Calibrated
1 = PCB Calibrated
(Completed by Factory)
SYS_MAG_CAL_STATUS
(UnitCalStatus)
300
Unit calibration completed status
R
Default:0
Six-bit bitmask of Calibration Status of Current Channels
0b000001 = channel 1 cal complete
0b000011 = channel 1 and 2 cal complete
0b111111 = channel 1 to 6 cal complete
HISTORY_LOG_STATUS
(HistoryLogStatus)
312
History Log Status Value
R
Default:0
Indicates Status of the History Log
0 = Initializing History Log
1 = Successfully Reading History
2 = Out of Bounds history register
3 = EEPROM is busy
STATUS_FILTER_A_RELAY_ACTION
(FilterStatusRelayAEn)
15
Filter status A relay action enable bit mask
R/W
Default:9 Range:0 to 65535
Reference Filter Status Table
To Enable desired status detections, enter bit mask from table by converting to decimal. If a status is active and the bit corresponding to that status in this mask is set, the relay will be activated.
0 = Disabled
65535 = All enabled
STATUS_FILTER_B_RELAY_ACTION
(FilterStatusRelayBEn)
16
Filter status B relay action enable bit mask
R/W
Default:49151 Range:0 to 65535
STATUS_LINE_RELAY_ACTION
(LineStatusRelayEn)
17
Line status relay action enable bit mask
R/W
Default:71 Range:0 to 65535
Reference Line Status Detection bits
To Enable desired status detections, enter bit mask from table by converting to decimal. If a status is active and the bit corresponding to that status in this mask is set, the relay will be activated
0 = Disabled
65535 = All enabled
STATUS_FILTER_LOAD_RELAY_ACTION
(LoadStatusRelayEn)
18
Filter load status relay action enable bit mask
R/W
Default:63 Range:0 to 65535
Reference load status detection bits table
To Enable desired status detections, enter bit mask from table by converting to decimal. If a status is active and the bit corresponding to that status in this mask is set, the relay will be activated.
0 = Disabled
65535 = All enabled
STATUS_FILTER_A_CNT_ACTION
(FilterStatusCntAEn)
19
Filter status A tune contactor action enable bit mask
R/W
Default:1 Range:0 to 65535
Reference Filter Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal.
0 = Disabled
65535 = All enabled
STATUS_FILTER_B_CNT_ACTION
(FilterStatusCntBEn)
20
Filter status B tune contactor action enable bit mask
R/W
Default:36863 Range:0 to 65535
STATUS_LINE_CNT_ACTION
(LineStatusCntEn)
21
Line status tune contactor action enable bit mask
R/W
Default:64 Range:0 to 65535
Reference Line Status Detection bits
To Enable desired status detections, enter bit mask from table by converting to decimal. If a status is active and the bit corresponding to that status in this mask is set, the relay will be activated
0 = Disabled
65535 = All enabled
STATUS_FILTER_LOAD_CNT_ACTION
(LoadStatusCntEn)
22
Filter load status tune contactor action enable bit mask
R/W
Default:0 Range:0 to 65535
Reference load Status Table in IOM
To enabled desired status detections, enter bit mask from table by converting to decimal.
0 = Disabled
65535 = All enabled
HISTORY_LOG_REQUEST
(HistReqCmd)
189
Status detection history record request command
R/W
Default:0
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal