Power Register Map

This register map contains parameters that are used to store and calculate the power output and input of the harmonic filter. Note that some parameters shown below may not exist in the parameter database/ or shown in PQVision. These parameters have been reserved for future use and are enabled in EtherNet/IP EDS File.
Note:
All parameters with an asterisk (*) in the description will require the Tech level access codes parameter key A: 0x007D (125) and parameter key B: 0xEA6E (60014). All parameters are enabled for communication to EtherNet/IP unless explicitly stated otherwise in the Notes Column of the Table.
Table
5
: Power Feedback and Setpoint Parameters Register Map
Parameter Name
(EtherNet Name)
Instance ID
Description
Type
Default & Ranges
Notes
P_LINE_APPARENT_TOTAL
(SLine)
258
Line apparent power,
(kVA)
R
Default:0
Range: 0 to 1000 kVAR
Total Filter input apparent power.
P_LINE_REAL_TOTAL
(PLine)
259
Line real power,
(kW)
R
Default:0
Range: 0 to 1000 kVAR
Total Filter input real power.
P_LINE_REACTIVE_TOTAL
(QLine)
260
Line reactive power,
(kVAR)
R
Default:0
Range: 0 to 1000 kVAR
Total Filter input reactive power: Negative number indicates inductive power;
Positive number indicates capacitive power.
P_LINE_POWER_FACTOR
(PFLine)
261
Line power factor,
(%)
R
Default:0
Range: -1000 to 1000
Filter input Displacement Power Factor – Negative value indicates lagging power factor.
1,000 = 1.00 Unity PF
-950 = 0.95 Lagging PF
950 = 0.95 Leading PF
P_LOAD_APPARENT_TOTAL
(SLoad)
262
Load apparent power,
(kVA)
R
Default:0
Range: 0 to 1000 kVAR
Total Filter output apparent power
P_LOAD_REAL_TOTAL
(PLoad)
263
Load real power,
(kW)
R
Default:0
Range: 0 to 1000 kVAR
Total Filter output real power
P_LOAD_REACTIVE_TOTAL
(QLoad)
264
Load reactive power,
(kVAR)
R
Default:0
Range: -1000 to 1000 kVAR
Total Filter output reactive power: Negative number indicates inductive power. Positive number indicates capacitive power
P_LOAD_POWER_FACTOR
(PFLoad)
265
Load power factor,
(%)
R
Default:0
Range: -1000 to 1000
Filter output Displacement Power Factor – Negative values indicate lagging power factor.
1,000 = 1.00 Unity PF
-950 = 0.95 Lagging PF
950 = 0.95 Leading PF
P_LOAD_REAL_MEAS
(PLoadAlt)
266
Measured Load real power,
(kW)
R
Default:0
NO_LOAD_CAP_CURRENT
(ITuneNoLoad)
308
Unit rated capacitance no load cap current,
(Farads)
R
Default:0
Range: 0 to 65535
Expected tune circuit current at no load in tenths of amps.
KVAR_EFFECTIVE
(KVAREffective)
309
Effective kVAR after applying kVAR factor,
(kVAR)
R
Default:0
Effective nameplate kVAR after kVAR factor. Used for kVAR contactor control 10 = 10KVAR
Range: -32768 to 32767
PF_KVAR_SLOPE
(KVARSlope)
310
Slope factor applied to nameplate kVAR for kVAR contactor control.
R
Default:0
Slope factor applied to nameplate kVAR for kVAR contactor control.
Range: -32768 to 32767
PF_KVAR_INTERCEPT
(KVARIntercept)
311
Intercept factor applied to nameplate kVAR for kVAR contactor control.,
(kVAR)
R
Default:0
Range: 0 to 65535
Intercept factor applied to nameplate kVAR for kVAR contactor control.
CNT_CLOSE_KVAR_THRESHOLD
(CntCloseKVARThrsh)
25
Contactor close threshold for kVAR control mode,
(kVAR)
R/W
Default:50
Range:0 to 1000
Contactor close threshold for kVAR control negative setpoint = lagging target positive setpoint = leading target
CNT_CLOSE_KVAR_HYSTERESIS
(CntCloseKVARHys)
26
Contactor close/open hysteresis in kVAR control mode,
(%)
R/W
Default:10
Range:5 to 100
Contactor will open when it reaches the hysteresis
SYS_PF_STEP_1_KVAR
(TuneKVAR1)
29
Tune circuit 1,
(kVAR)
R/W
Default:5
Range:0 to 500
Desired filter kVAR for contactor to enable
SYS_PF_STEP_2_KVAR
(TuneKVAR2)
30
Tune circuit 2,
(kVAR)
R/W
Default:5
Range:0 to 500
Filter Second Tuned Circuit kVAR (Only used for filters with dual tuned circuits)
PF_KVAR_FACTOR_NL
(KVARFactorNL)
185
Factor applied to nameplate kVAR at no load for kVAR contactor control
R/W
Default:105
Range:100 to 140
100 = 1.0
PF_KVAR_FACTOR_FL
(KVARFactorFL)
186
Factor applied to nameplate kVAR at full load for kVAR contactor control
R/W
Default:115
Range:100 to 140
100 = 1.0
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.