Loading

Redundancy Module Configuration Tool - Multiple Vulnerabilities

Severity:
High
Advisory ID:
SD1800
Data pubblicazione:
September 01, 2026
Ultimo aggiornamento:
September 01, 2026
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
No
Corrected:
Sì
Workaround:
No
CVE IDs
CVE-2026-9633,
CVE-2026-9634
Download
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
JSON
Riepilogo

The security of our products is important to us as your industrial automation supplier. This security issue was found internally during routine testing and is being reported based on our commitment to customer transparency and improvement of all business environments.

Product Description

The Redundancy Module Configuration Tool from Rockwell Automation is a software utility used to configure and manage ControlLogix® Redundancy Modules (1756-RM2 and 1756-RM3), supporting setup, diagnostics, and maintenance of redundancy systems in critical industrial environments.

Affected Products and Solution

Affected Product

CVE

Affected Software Version

Corrected in Software Version

Affected Catalog Numbers

Redundancy Module Configuration Tool

CVE-2026-9633

10.00.00

10.01.00

None

Redundancy Module Configuration Tool

CVE-2026-9634

9.00.00 through 10.00.00

10.01.00

None

Security Issue Details for CVE-2026-9633

Category

Details

CVE ID

CVE-2026-9633

Impact

A security issue exists within the Redundancy Module Configuration Tool. The RM3ConfigTool.exe binary searches directories in the system path for a required DLL, and one or more of these directories may be writable by standard (non-administrator) users due to incorrect default permissions. If a local attacker places a malicious DLL in such a directory and an administrator subsequently runs the tool, the malicious DLL is loaded into the elevated process and executes with Administrator/SYSTEM privileges.

 

CVSS 3.1 Base Score

7.3/10

CVSS 4.0 Base Score

7.0/10

CWE

CWE-276: Incorrect Default Permissions

Known Exploited Vulnerability

No

Security Issue Details for CVE-2026-9634

Category

Details

CVE ID

CVE-2026-9634

Impact

A security issue exists within the Redundancy Module Configuration Tool. The RMConfigTool.exe binary searches directories in the system path for a required DLL, and one or more of these directories may be writable by standard (non-administrator) users due to incorrect default permissions. If a local attacker places a malicious DLL in such a directory and an administrator subsequently runs the tool, the malicious DLL is loaded into the elevated process and executes with Administrator/SYSTEM privileges.

 

 

CVSS 3.1 Base Score

7.3/10

CVSS 4.0 Base Score

7.0/10

CWE

CWE-276: Incorrect Default Permissions

Known Exploited Vulnerability

No

Mitigations and Workarounds
Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices. 

Revision History

Revision

Date

Description

1.0

9/1/2026

Initial release

Glossary:

·        Arbitrary Code Execution: an attacker's ability to run any commands or code of the attacker's choice on a target machine or in a target process

·        DLL (Dynamic Link Library): a file containing reusable code and data that can be loaded by Windows applications at runtime to provide shared functionality, reducing redundancy and enabling modular software design.

Get Up-to-Date Product Security Information

Visit the Rockwell Automation security advisories on the Trust Center page to:

·        Subscribe to product security alerts

·        Review the current list of Rockwell Automation security advisories

·        Report a possible security issue in a Rockwell Automation product

·        Learn more about the vulnerability policy

Support

If you have any questions regarding the security issue(s) above and how to mitigate them, contact TechConnect for help. More information can be found at Contact Us | Rockwell Automation | US.

If you have any questions regarding this disclosure, please contact PSIRT
Email: rasecure@ra.rockwell.com

Legal Disclaimer

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Home Rockwell Automation
  2. Chevron LeftChevron Left Trust Center
  3. Chevron LeftChevron Left Industrial Security Adv
  4. Chevron LeftChevron Left Industrial Security Advisory Detail
I testi di questo sito sono stati tradotti utilizzando l'intelligenza artificiale (AI) senza revisione o modifica da parte di esseri umani. I testi possono contenere errori o imprecisioni e sono forniti “così come sono” senza alcun tipo di garanzia. Il testo ufficiale è la versione inglese del contenuto.
Aggiorna le tue preferenze sui cookie per continuare.
Questa funzionalità richiede i cookie per migliorare la tua esperienza. Ti preghiamo di aggiornare le tue preferenze per consentire questi cookie:
  • Cookie dei social media
  • Cookie funzionali
  • Cookie di prestazione
  • Cookie di marketing
  • Tutti i cookie
Puoi aggiornare le tue preferenze in qualsiasi momento. Per ulteriori informazioni consultare il nostro {0} politica sulla riservatezza
CloseClose