Studio 5000 Logix Designer® – Multiple Vulnerabilities

Severity:
Medium,
High
Advisory ID:
SD1783
Date de publication:
July 14, 2026
Date de la dernière mise à jour:
July 14, 2026
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
Non
Corrected:
Oui
Workaround:
Non
CVE IDs
CVE-2026-9108 ,
CVE-2026-9127 ,
CVE-2026-9128
Téléchargements
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
JSON
JSON
Résumé

The security of our products is important to us as your industrial automation supplier. This security issue was found internally during routine testing and is being reported based on our commitment to customer transparency and improvement of all business environments.

Product Description

Studio 5000® is Rockwell Automation's integrated design environment for developing, programming, and managing industrial automation systems using Logix 5000® controllers.

Affected Products and Solution

Affected Product

CVE

Affected Software Version

Corrected in Software Version

Affected Catalog Numbers

Studio 5000 Logix Designer®

CVE-2026-9108

V36.00, 35.00,35.01, 34.00-34.03, 33.00-33.03, 32.00-32.04 and older

 

V37.00. 36.01, 35.02, 34.04, 33.04, 32.05

N/A

Studio 5000 Logix Designer®

CVE-2026-9127

V35.00,34.00,34.01, 33.00,33.02, 32.00-32.04 and older

 

V36.00, 35.01, 34.02, 33.02,32.05

 

N/A

Studio 5000 Logix Designer®

CVE-2026-9128

V35.00, 34.00-34.02, 33.00-33.02, 32.00-32.04 and older

 

 

V36.00, 35.01, 34.03, 33.03,32.05

 

N/A

Security Issue Details for CVE-2026-9108

Category

Details

CVE ID

CVE-2026-9108

Impact

A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.

 

CVSS 3.1 Base Score

6.7/10

CVSS 4.0 Base Score

5.4/10

CWE

CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')

Known Exploited Vulnerability

No

Security Issue Details for CVE-2026-9127

Category

Details

CVE ID

CVE-2026-9127

Impact

A remote code execution security issue exists within Studio 5000 Logix Designer® due to incorrect authorization on a configuration file. This can allow any authenticated user to modify the paths of external tools configured within the application. If exploited, an attacker could alter the configuration to point to a malicious executable, resulting in arbitrary code execution when any user interacts with the external tools functionality.

CVSS 3.1 Base Score

7.5/10

CVSS 4.0 Base Score

7.3/10

CWE

CWE-863: Incorrect Authorization

Known Exploited Vulnerability

No

Security Issue Details for CVE-2026-9128

Category

Details

CVE ID

CVE-2026-9128

Impact

A code execution security issue exists within Studio 5000 Logix Designer® due to an unquoted search path in the External Tools configuration. The executable paths specified in the external tools configuration file are not properly quoted, and because these paths contain spaces, the operating system may resolve them to unintended executables placed earlier in the search order. If exploited, an attacker could plant a malicious executable in a location within the search path, resulting in arbitrary code execution with the same permissions of the user running the application.

CVSS 3.1 Base Score

7.5/10

CVSS 4.0 Base Score

7.3/10

CWE

CWE-428: Unquoted Search Path or Element

Known Exploited Vulnerability

No

Mitigations and Workarounds
Customers using the affected software, who are not able to upgrade to one of the corrected versions, should use our security best practices. 

Revision History

Revision

Date

Description

1.0

7/14/2026

Initial release

Glossary:

·         Directory Traversal: also known as path traversal, is a security vulnerability that allows attackers to access files and directories outside the intended scope of a web application or system.

·         Arbitrary Code Execution: an attacker's ability to run any commands or code of the attacker's choice on a target machine or in a target process

Get Up-to-Date Product Security Information

Visit the Rockwell Automation security advisories on the Trust Center page to:

·         Subscribe to product security alerts

·         Review the current list of Rockwell Automation security advisories

·         Report a possible security issue in a Rockwell Automation product

·         Learn more about the vulnerability policy

Support

If you have any questions regarding the security issue(s) above and how to mitigate them, contact TechConnect for help. More information can be found at Contact Us | Rockwell Automation | US.

If you have any questions regarding this disclosure, please contact PSIRT
Email: rasecure@ra.rockwell.com

Legal Disclaimer

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Accueil Rockwell Automation
  2. Chevron LeftChevron Left Trust Center
  3. Chevron LeftChevron Left Industrial Security Adv
  4. Chevron LeftChevron Left Industrial Security Advisory Detail
Le contenu de ce site a été traduit à l’aide de l’intelligence artificielle (IA) sans relecture ni édition humaines. Il est susceptible de contenir des erreurs et imprécisions et il est livré « tel quel », sans garantie d’aucune sorte. Le texte qui fait foi est la version anglaise.
Veuillez mettre à jour vos préférences en matière de cookies pour continuer.
Cette fonctionnalité nécessite des cookies pour améliorer votre expérience. Veuillez mettre à jour vos préférences pour autoriser ces cookies:
  • Cookies de réseaux sociaux
  • Cookies fonctionnels
  • Cookies de performances
  • Cookies marketing
  • Tous les cookies
Vous pouvez mettre à jour vos préférences à tout moment. Pour plus d'informations, veuillez consulter notre {0} politique de confidentialité
CloseClose