Loading

ControlLogix® Ethernet Remote Code Execution Vulnerability

Severity:
Critical
Advisory ID:
SD1732
Fecha de publicación:
August 14, 2025
Última actualización:
August 14, 2025
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
No
Corrected:
Sí
Workaround:
No
CVE IDs
CVE-2025-7353
Descargas
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
Resumen

Published Date: 8/14/2025 

Last Updated: 8/14/2025 
Revision Number: 1.0 
CVSS Score: 9.8/10 

The security of our products is important to us as your chosen industrial automation supplier. This anomaly was found internally during routine testing and is being reported based on our commitment to customer transparency and to improve their business or production environments. 

AFFECTED PRODUCTS AND SOLUTION

Affected Product 

CVE 

Affected Software Versions 

Corrected in Software Version 

1756-EN2T/D

CVE-2025-7353 

Version 11.004 or below 

12.001 

1756-EN2F/C

CVE-2025-7353 

Version 11.004 or below 

12.001 

1756-EN2TR/C

CVE-2025-7353 

Version 11.004 or below 

12.001 

1756-EN3TR/B

CVE-2025-7353 

Version 11.004 or below 

12.001 

1756-EN2TP/A

CVE-2025-7353 

Version 11.004 or below 

12.001 

 

VULNERABILITY DETAILS

Rockwell Automation used the latest version of the CVSS scoring system to assess the following vulnerabilities. 

CVE-2025-7353 IMPACT

A security issue exists due to the web-based debugger agent enabled on released devices. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow.  

CVSS 3.1 Base Score: 9.8 
CVSS 3.1 Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

CVSS 4.0 Base Score: 9.3 
CVSS 4.0 Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N

CWE: CWE-1188: Initialization of a Resource with an Insecure Default 
Known Exploited Vulnerability (KEV) database: No 

Mitigations and Workarounds 
Users should update to the corrected version if possible. If users using the affected software are not able to upgrade the version, security best practices should be applied. 

·         Security Best Practices

 

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Página principal de Rockwell Automation Chevron RightChevron Right
  2. Chevron LeftChevron Left Trust Center Chevron RightChevron Right
  3. Chevron LeftChevron Left Industrial Security Adv Chevron RightChevron Right
  4. Chevron LeftChevron Left Industrial Security Advisory Detail Chevron RightChevron Right
Actualice sus preferencias de cookies para continuar.
Esta función requiere cookies para mejorar su experiencia. Actualice sus preferencias para permitir estas cookies.:
  • Cookies de Redes Sociales
  • Cookies Funcionales
  • Cookies de Performance
  • Cookies de Marketing
  • Todas las cookies
Puede actualizar sus preferencias en cualquier momento. Para más información, vea nuestro {0} Política de Privacidad
CloseClose