Module Data Types 1794-IB16XOB16P
    The table below lists and describes the module-defined data types for the 1794-IB16XOB16P Combo module. It includes information for input (as indicated by an "I"), output (as indicated by an "O") and configuration (as indicated by a "C").
| Tip: | FLEX I/O is based on 16-bit INTs and not 32-bit DINTs. Using 16-bit INTs in instructions that are optimized for 32-bit DINTs may decrease performance with certain instructions. | 
Module-defined Data Type: AB: 1794_IB16XOB16P:I:0
This module-defined data type does not apply to modules having Rack Optimization selected for the Comm Format and does not appear among the Module Tags in the RSLogix software.
| Member Name | Type | Default  Display Style | Description | 
| Fault | DINT | Binary | Fault - Used for Input Data Validation 0 = Valid Data 1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 bits are set to 1. | 
| Data | INT | Binary | Input data for the module. | 
Module-defined Data Type: AB:1794_IB16XOB16P:O:0
| Member Name | Type | Default  Display Style | Description | 
| Data | INT | Binary | Output data for the module. | 
Module-defined Data Type: AB:1794_IB16XOB16P:C:0
| Member Name | Type | Default  Display Style | Description | 
| Filter_0 | BOOL | Decimal | Indicates the delay time for the module. | 
| Filter_1 | BOOL | Decimal | Indicates the delay time for the module. | 
| Filter_2 | BOOL | Decimal | Indicates the delay time for the module. | 
| SSData | INT | Binary | 