Loading

RSLinx Classic Third-Party Vulnerability CVE-2020-13573

Severity:
High
Advisory ID:
SD1774
Published Date:
June 16, 2026
Last Updated:
June 16, 2026
Revision Number:
1.0
Known Exploited Vulnerability (KEV):
No
Corrected:
Yes
Workaround:
No
CVE IDs
CVE-2020-13573
Downloads
The following link(s) provide the security advisory in Vulnerability Exploitability Exchange format:
JSON
Summary
RSLinx Classic Third-Party Vulnerability CVE-2020-13573

The security of our products is important to us as your industrial automation supplier. This security issue is being reported based on our commitment to customer transparency and improvement of all business environments.

Product Description

RSLinx ® Classic permits 3rd-party software to access data from Rockwell Automation controllers using OPC DA or DDE interface. The software is well suited to work with older software and systems containing older hardware and networks.

Affected Products and Solution

Affected Product

CVE

Affected Software Version

Corrected in Software Version

RSLinx® Classic

CVE-2020-13573

4.50.00 and earlier

4.60.00

Security Issue Details for CVE-2020-13573

Category

Details

CVE ID

CVE-2020-13573

Impact

A denial-of-service vulnerability exists in the Ethernet/IP server functionality of  RSLinx Classic. A specially crafted network request can lead to a denial of service. If exploited, the application will become unresponsive and will not recover on its own. A user would need to manually restart RSLinx Classic to restore normal operation.

CVSS 3.1 Base Score

7.5/10

CVSS 4.0 Base Score

8.7/10

CWE

CWE-125: Out-of-bounds Read

Known Exploited Vulnerability

No (Not listed in KEV database)

 

Mitigations and Workarounds
Customers using the affected software, who are not able to upgrade to one of the corrected versions, should consider applying the available patch (BF31213) for their current version or applying the  recommended security best practices.

Revision History

Revision

Date

Description

1.0

06/16/2026

Initial release

Glossary:

·         Denial of Service (DoS): A malicious attempt to disrupt the normal functioning of a targeted server, service, or network by overwhelming it with a flood of traffic or triggering a crash.

·         OPC DA (OPC Data Access): A client-server communication standard used in industrial automation that enables real-time exchange of process data between control devices and software applications.

·         DDE (Dynamic Data Exchange): A legacy inter-process communication protocol used in Windows-based applications to share data between programs in real time.

Get Up-to-Date Product Security Information

Visit the Rockwell Automation security advisories on the Trust Center page to:

·         Subscribe to product security alerts

·         Review the current list of Rockwell Automation security advisories

·         Report a possible security issue in a Rockwell Automation product

·         Learn more about the vulnerability policy

Support

If you have any questions regarding the security issue(s) above and how to mitigate them, contact TechConnect for help. More information can be found at Contact Us | Rockwell Automation | US.

If you have any questions regarding this disclosure, please contact PSIRT
Email: rasecure@ra.rockwell.com

Legal Disclaimer

ROCKWELL AUTOMATION DOES NOT WARRANT THE COMPLETENESS, TIMELINESS OR ACCURACY OF ANY OF THE DATA CONTAINED IN THIS WEB SITE AND MAY MAKE CHANGES THERETO AT ANY TIME IN ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS "AS IS." IN NO EVENT SHALL ROCKWELL BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT OR DAMAGE, EVEN IF ROCKWELL AUTOMATION HAVE BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES. ROCKWELL AUTOMATION DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED IN RESPECT OF THE INFORMATION (INCLUDING SOFTWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not countenance the exclusion of implied warranties; thus, this disclaimer may not apply to you.

Rockwell Automation Home
Copyright ©2022 Rockwell Automation, Inc.
  1. Chevron LeftChevron Left Rockwell Automation Home
  2. Chevron LeftChevron Left Trust Center
  3. Chevron LeftChevron Left Industrial Security Adv
  4. Chevron LeftChevron Left Industrial Security Advisory Detail
Please update your cookie preferences to continue.
This feature requires cookies to enhance your experience. Please update your preferences to allow for these cookies:
  • Social Media Cookies
  • Functional Cookies
  • Performance Cookies
  • Marketing Cookies
  • All Cookies
You can update your preferences at any time. For more information please see our {0} Privacy Policy
CloseClose