ControlLogix 8 Pt A/O HART Isolated

PrintPrint
Print
EmailEmail
Share
Product RegistrationProduct Registration
QR code
Allen-Bradley 1756-OF8IH product image
Lifecycle status: Active
Product at a glance
Repair Options Available
Lifecycle status: Active
Product at a glance
Repair Options Available
Add to BoM
  • Get Support
Technical Specifications
General
Electrical
Environmental
Mechanical
Certification
Power
Construction
Drawings
Documents
Downloads
Certifications
Alternative Products
Technotes
Isolation
250V (continuous), Reinforced insulation type, outputs to backplane. Basic insulation type, output to output, and outputs to ground.
Number Of Channels
8
Output Signal
4-20mA
Input, current
True
Input, voltage
True
Input, resistor
False
Input, resistance thermometer
False
Input, thermocouple
False
Input signal, configurable
True
Output, current
False
Output, voltage
False
Output signal configurable
False
Analogue inputs configurable
True
Analogue outputs configurable
False
Type of electric connection
Screw-/spring clA connection
Wire type
Copper
Output range
0...20mA @ 4...20mA
Load reactance
10 µH maximum
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Module keying
Electronic, software configurable
Offset drift
±3 ppm of full scale range/°C (72 nA/°C typical)
Output conversion method
R-Ladder DAC
Outputs
8 current
Open circuit detection
Current output only (output must be set >=0.1 mA)
Drive capability
50...750 Ω with short circuit survival
Data format
IEEE 32-bit floating point
Wire category
2 - on signal ports
Overvoltage protection
±24V DC
Module error
0.3% @ 4...20mA
Gain drift with temperature
±4 ppm of full scale range/°C
Voltage and current ratings
Backplane: 220mA @ 5.1V DC, 360mA @ 24V DC, Output voltage range: 5...30V DC, Output current range: 0...20mA @ 4...20mA
Settling time
HART not enabled: <23 ms to 95% with resistive loads, HART enabled: <100 ms to 95% with resistive loads
Module scan time
Estimate 1 s if all channels are HART enabled, Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
Current draw
400 mA (estimated) @ 24V @ 24V
Power dissipation
6.5 W nominal (maximum), (<6.4 W with 50 Ω load on all channels), (<6.5 W with 250 Ω load on all channels), (<6.7 W with 750 Ω load on all channels)
Resolution
15 bit across 24 mA, 732 nA per bit
Wire size
Single wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
Calibrated accuracy
0.15% @ 4...20mA, 25 °C (77 °F)
Suitable for safety functions
False
Output short circuit protection
Current electronically limited to <=21 mA with no damage
Surrounding air temperature, max
60 °C
North American temperature code
T4A
Emissions
IEC 61000-6-4
ESD immunity
6 kV contact discharges, 8 kV air discharges
EFT/B immunity
±2kV @ 5kHz on signal ports
Relative humidity
5...95% noncondensing
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Surge transient immunity
±2kV line-earth (CM) on shielded ports
Operating temperature
0 °C <60 °C (32 °F <140 °F)
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature
-40 °C
RTB keying
User-defined mechanical
Vibration
2 G @ 10...500 Hz
Shock
Operating: 30 G, Non operating: 50 G
Slot width
1
Calibration interval
12 mo typical
ATEX temperature code
T4
IECEx temperature code
T4
Isolation voltage
250V (continuous), Reinforced insulation type, outputs to backplane, Basic insulation type, output to output, and outputs to ground.
Enclosure type rating
None (open-style)
Sign in to your Rockwell Automation account to view and download technical drawings.
Sign In
Type Resource Publication
General Product Cutsheet --
General 1756-OF8IH in Current Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-191 Rev 01 --
General 1756-OF8IH in Voltage Mode with 1492-AIFM6S-3 or 1492-RAIFM6S-3 41171-193 Rev 1 --
General Product Profile --
General Technical Detail --
General 1756-OF8IH in Voltage Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-196 Rev 1 --
Technical Data 1756-td002_-en-e 1756-TD002
User Manual 1756-um533_-en-p 1756-UM533
Looking for more documentation?
Find curated technical documentation for this product in the Technical Documentation Center, or search our full Literature Library.
Visit the Technical Documentation Center Search the Literature Library
Available Downloads
  • DTM Library Software for the 1756-OF8IH Module v1.001
  • Firmware for 1756-OF8IH v1.001
  • EDS files for 1756-OF8IH (multi)
  • EDS files for ControlLogix Family (multi)
  • AOP - Add On Profiles for 1756 HART I/O v40.12.23
See All Downloads
China CCC
  • China CCC
  • MOROCCO DOC

This product was certified with the above certifications as of 2025-09-10. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.

Items Per Page:
1-1 of 1
Looking for more Technotes?
Find questions and answers from Rockwell Automation technical experts for this product in our Knowledgebase.
Search Knowledgebase
Technical Specifications
Isolation
250V (continuous), Reinforced insulation type, outputs to backplane. Basic insulation type, output to output, and outputs to ground.
Number Of Channels
8
Output Signal
4-20mA
Input, current
True
Input, voltage
True
Input, resistor
False
Input, resistance thermometer
False
Input, thermocouple
False
Input signal, configurable
True
Output, current
False
Output, voltage
False
Output signal configurable
False
Analogue inputs configurable
True
Analogue outputs configurable
False
Type of electric connection
Screw-/spring clA connection
Wire type
Copper
Output range
0...20mA @ 4...20mA
Load reactance
10 µH maximum
Terminal block torque specifications
1756-TBCH: 0.5 Nm (4.4 in-lb)
Module keying
Electronic, software configurable
Offset drift
±3 ppm of full scale range/°C (72 nA/°C typical)
Output conversion method
R-Ladder DAC
Outputs
8 current
Open circuit detection
Current output only (output must be set >=0.1 mA)
Drive capability
50...750 Ω with short circuit survival
Data format
IEEE 32-bit floating point
Wire category
2 - on signal ports
Overvoltage protection
±24V DC
Module error
0.3% @ 4...20mA
Gain drift with temperature
±4 ppm of full scale range/°C
Voltage and current ratings
Backplane: 220mA @ 5.1V DC, 360mA @ 24V DC, Output voltage range: 5...30V DC, Output current range: 0...20mA @ 4...20mA
Settling time
HART not enabled: <23 ms to 95% with resistive loads, HART enabled: <100 ms to 95% with resistive loads
Module scan time
Estimate 1 s if all channels are HART enabled, Pass through messages, handheld communications, sary masters, communication errors, or configuration changes can significantly increase the update time.
Current draw
400 mA (estimated) @ 24V @ 24V
Power dissipation
6.5 W nominal (maximum), (<6.4 W with 50 Ω load on all channels), (<6.5 W with 250 Ω load on all channels), (<6.7 W with 750 Ω load on all channels)
Resolution
15 bit across 24 mA, 732 nA per bit
Wire size
Single wire connection (1756-TBCH): 0.33...2.1 mm² (22...14 AWG) solid or stranded shielded copper wire, rated at 105 °C (221 °F) or greater, 1.2 mm (3/64 in.) insulation maximum, Single wire connection (1756-TBS6H): 0.33...2.1 mm² (22...14 AWG) solid or
Calibrated accuracy
0.15% @ 4...20mA, 25 °C (77 °F)
Suitable for safety functions
False
Output short circuit protection
Current electronically limited to <=21 mA with no damage
Surrounding air temperature, max
60 °C
North American temperature code
T4A
Emissions
IEC 61000-6-4
ESD immunity
6 kV contact discharges, 8 kV air discharges
EFT/B immunity
±2kV @ 5kHz on signal ports
Relative humidity
5...95% noncondensing
Conducted RF immunity
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Surge transient immunity
±2kV line-earth (CM) on shielded ports
Operating temperature
0 °C <60 °C (32 °F <140 °F)
Radiated RF immunity
10 V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 900 MHz, 10 V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz, 3 V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
Nonoperating temperature
-40 °C
RTB keying
User-defined mechanical
Vibration
2 G @ 10...500 Hz
Shock
Operating: 30 G, Non operating: 50 G
Slot width
1
Calibration interval
12 mo typical
ATEX temperature code
T4
IECEx temperature code
T4
Isolation voltage
250V (continuous), Reinforced insulation type, outputs to backplane, Basic insulation type, output to output, and outputs to ground.
Enclosure type rating
None (open-style)
Drawings
Sign in to your Rockwell Automation account to view and download technical drawings.
Sign In
Documents
Product Cutsheet General
--
1756-OF8IH in Current Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-191 Rev 01 General
--
1756-OF8IH in Voltage Mode with 1492-AIFM6S-3 or 1492-RAIFM6S-3 41171-193 Rev 1 General
--
Product Profile General
--
Technical Detail General
--
1756-OF8IH in Voltage Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-196 Rev 1 General
--
1756-td002_-en-e Technical Data
1756-TD002
1756-um533_-en-p User Manual
1756-UM533
Type Resource Publication
General Product Cutsheet --
General 1756-OF8IH in Current Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-191 Rev 01 --
General 1756-OF8IH in Voltage Mode with 1492-AIFM6S-3 or 1492-RAIFM6S-3 41171-193 Rev 1 --
General Product Profile --
General Technical Detail --
General 1756-OF8IH in Voltage Mode with 1492-AIFM8S-3 or 1492-RAIFM8S-3 41171-196 Rev 1 --
Technical Data 1756-td002_-en-e 1756-TD002
User Manual 1756-um533_-en-p 1756-UM533
Looking for more documentation?
Find curated technical documentation for this product in the Technical Documentation Center, or search our full Literature Library.
Visit the Technical Documentation Center Search the Literature Library
Downloads
Available Downloads
  • DTM Library Software for the 1756-OF8IH Module v1.001
  • Firmware for 1756-OF8IH v1.001
  • EDS files for 1756-OF8IH (multi)
  • EDS files for ControlLogix Family (multi)
  • AOP - Add On Profiles for 1756 HART I/O v40.12.23
See All Downloads
Certifications
China CCC
  • China CCC
  • MOROCCO DOC

This product was certified with the above certifications as of 2025-09-10. Products sold before or after this date might carry different certifications. Please review the product label to check for the certifications your specific product carries.

Alternative Products
Items Per Page:
1-1 of 1
Technotes
Looking for more Technotes?
Find questions and answers from Rockwell Automation technical experts for this product in our Knowledgebase.
Search Knowledgebase
Loading
Find your nearest distributor
Contact your distributor in {0}
Change location
EmailEmail
PhonePhone
Find a partner
ControlLogix 8 Pt A/O HART Isolated
CloseClose
1756-OF8IH
Close
Print
Allen-Bradley 1756-OF8IH product image
Phone:
Call
Rockwell Automation Home
Copyright ©2025 Rockwell Automation, Inc.
Sign in to your Rockwell Automation account to submit a repair documentation request.
Sign In
Request repair documentation
All fields with * are required for processing your request.
This field is required
This field is required
This field is required
This field is required
This field is required
Documentation of liability insurance is required for anyone who is requesting documentation for product repairs.
UploadUpload
Please upload documentation of liability insurance.*
1 file selected
CloseClose
File size is too large. Must be less than 5 MB.
Accepted file types: zip, pdf; Maximum size: 5 MB.
Right to Repair Terms and Conditions
Rockwell Automation is making, parts, and service documentation available at your request in compliance with applicable right to repair laws and regulations. By signing below, you are agreeing to the following terms and conditions of your purchase of Rockwell Automation genuine repair parts for repair of a Rockwell Automation product. As used below, “Self Service Repair Parts” means genuine Rockwell Automation parts (components of Rockwell Automation products) purchased from Rockwell Automation for installation in a Rockwell Automation product as part of a Self Service Repair. Self Service Repair Parts may be new or previously used genuine Rockwell Automation parts that have been tested and passed Rockwell Automation functional requirements. “Self Service Repair Tools” means equipment and related materials purchased for the purpose of performing repairs.
Your request has been successfully submitted.
Please allow up to 5 business days to receive a response to your inquiry.
  1. Chevron LeftChevron Left Rockwell Automation Home
  2. Chevron LeftChevron Left Products
Please update your cookie preferences to continue.
This feature requires cookies to enhance your experience. Please update your preferences to allow for these cookies:
  • Social Media Cookies
  • Functional Cookies
  • Performance Cookies
  • Marketing Cookies
  • All Cookies
You can update your preferences at any time. For more information please see our {0} Privacy Policy
CloseClose