View the Event Log

On the Event Log tab of the RMCT, you can view a history of events for both partner redundancy modules. You can save the system event history to nonvolatile memory and export Tech Support logs to send to Technical Support.
Event Log
Event Log in RMCT
Event Log Parameters
Parameter
Description
Event No.
A unique, sequential number to identify the event.
Time Stamp
The date and time that the event was logged.
Event Class
A broad category to classify the event.
Basic Info
A basic description of the event.
Extended Info 1
Extended Info 2
Additional information that is related to the basic description of the event.
Extended information is not available for every event.

Event Classes

The following event classes can appear in the Event Class column in the event log.
Event Classes
Event Class
Description
Qualification Event
An event that is related to chassis qualification.
For example, the qualification process succeeded.
Disqualification Event
An event that is related to chassis disqualification.
For example, the Disqualify Secondary command was issued.
Switchover Event
An event that is related to a chassis switchover.
For example, the Initiate Switchover command was issued.
RM Fault Event
One of the redundancy modules had a major or minor fault.
For recovery information, see the Code field in the fault log on the Module Info tab. See Redundancy Module Faults.
User configuration change event
A redundancy module configuration parameter has been changed. For example, if you change the Auto-synchronization parameter from Always to Never, an event that is classified as Configuration is logged.
Redundancy state has changed
The state of a redundancy module changed. For example, the redundancy module lost its partner.
Chassis State Changed
The state of the redundant chassis pair changed. For example, the redundancy status changed from disqualified secondary to qualified secondary.
Idle Qualified
An event occurred while the chassis was in an idle qualified state. The event caused the chassis to leave the idle qualified state.
Idle Disqualified
An event occurred while the chassis was in an idle disqualified state. The event caused the chassis to leave the idle disqualified state.
General
An event unrelated to the redundancy state or a redundancy action.

Event Log Examples

This section contains example event log entries for typical system events.
Manual Switchover
Event Class
Basic Info
Extended Info 1
Extended Info 2
Switchover Event
Commanded switchover
—
—
Manual Disqualification
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Commanded disqualification
—
—
Qualification Successful
Event Class
Basic Info
Extended Info 1
Extended Info 2
Qualification Event
Qualification succeeded
Qualification succeeded
—
Qualification Failed Due to Incompatible Module
Event Class
Basic Info
Extended Info 1
Extended Info 2
Qualification Event
Qualification Abort
Qualification aborted due to some modules not having fully compatible partners
Bitmap of compatibility assessment for modules in chassis
Switchover Due to Module Removal from Primary
Event Class
Basic Info
Extended Info 1
Extended Info 2
Switchover Event
Redundancy Manager State: Disqualified Secondary With Primary
—
—
Switchover Due to Network Cable Removal in Primary Event Class
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Communication on switchover was lost, switchover processed with uncoordinated manner.
Switchover
—
Switchover Due to Chassis Power Fault in Primary Chassis
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Qualification Abort - Primary Module Screamed on Partner
—
Disqualification Due to Network Connection Lost between Primary and Secondary Chassis
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Qualification Abort - Disqualify command
—
Disqualification Due to Partner Chassis Power Fault
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Partner Redundancy Module has major nonrecoverable fault
—
Disqualification Due to Partner Chassis Module Removal
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Qualification Abort - Module Removal
—
Disqualification Due to Partner Chassis Redundancy Module Fault
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Qualification Abort - Disqualify command
—
Disqualification Due to Redundancy Module Fiber Cable Disconnected or Faulted
Event Class
Basic Info
Extended Info 1
Extended Info 2
Disqualification Event
Qualification Abort
Qualification aborted due to lack of partner RM.
—