Scenario 3 - Replacement Device SNN is Different from Original and No Safety Signature Exists

  1. Remove the old I/O device and install the new device.
  2. Right-click your safety I/O device and select Properties.
  3. In the navigation pane, click Safety.
  4. Click Reset Ownership.
    This image shows where to reset the configuration ownership in Logix Designer.
  5. Click OK.
  6. Follow your company-prescribed procedures to functionally test the replaced I/O device and system and to authorize the system for use.