Scenario 2 - Replacement Device SNN is Different from Original and Safety Signature Exists
- Remove the old I/O device and install the new device.
- Right-click your safety I/O device and select Properties.
- In the navigation pane, click Safety.
- Click Reset Ownership.

- Click OK.
- Right-click the device and select Properties.
- Click the ellipse to the right of the safety network number to open the Safety Network Number dialog box.

- Click Set.

- Verify that the Network Status (NS) status indicator is alternating red/green on the correct device before clicking Yes on the confirmation dialog box to set the SNN and accept the replacement device.
- Follow your company-prescribed procedures to functionally test the replaced I/O device and system and to authorize the system for use.