Create and Configure I/O
In the
Studio 5000 Logix Designer
application add all the I/O and Communication modules that are part of the project. This allows the controller to communicate with the modules. When you configure an I/O module, you specify characteristics specific to that module. The
Studio 5000 Logix Designer
application automatically adds the predefined tags for the module as controller-scoped tags.The configuration information for the module depends on the module you select.
You can specify electronic keying to restrict a connection to a specific module type. Electronic keying ensures that a module being inserted or configured is the proper type.
Repeat this process for all of the modules your project works with.
To create and configure I/O
- In theController Organizer, expand theI/O Configurationfolder, right-click a network or backplane and chooseNew Module.
- TheSelect Module Typedialog opens.
- Choose the module type to create:
- Catalog - Choose from a list of modules that is valid for the current context
- Module Discovery - Perform online module discovery to find attached physical devices on a network or backplane
- Favorites - A custom list of module types
- After selecting the module, selectOK.
- TheNew Moduledialog box opens from which you can complete the process of creating and configuring the I/O module.Enter the configuration information for the module you are creating.
- Name - Enter a name for the module, this name is appended to the catalog number in theController Organizer.
- IP Address - For Ethernet connected modules, the IP address is required.For other settings, the default values are automatically applied.
- SelectOK. The new module is displayed in theController Organizer.Double-click the module in theController Organizerto open it and review the default settings and edit them if needed.