Cosine (COS)

The COS instruction takes the cosine of the Source value (in radians) and stores the result in the Destination. The COS operator/function computes the cosine of Source and returns the floating point result. The resulting value is always greater than or equal to -1 and less than or equal to 1.
Available Languages
Ladder Diagram
COS_LD_avail_v31
Function Block Diagram
Function Block Diagram supports these elements:
FBD Block
COS_FBD_avail_v31
FBD Function
COS_avail_FBDFunction
Structured Text
This instruction is not available in structured text.
TIP: Use COS as an operator in an expression to compute the same result. Refer to Structured Text Syntax for more information on the syntax of expressions and assignments within structured text.
Operands
IMPORTANT: Unexpected operation may occur if:
  • Output tag operands are overwritten.
  • Members of a structure operand are overwritten.
  • Except when specified, structure operands are shared by multiple instructions.
There are data conversion rules for mixing numeric data types within an instruction. See Data Conversions.
Ladder Diagram
Operand
Data Type
Format
Description
Source
SINT
INT
DINT
LINT
USINT
UINT
UDINT
ULINT
REAL
LREAL
Immediate
tag
Value to convert to cosine.
Destination
REAL
LREAL
tag
Tag to store result of the instruction.
Function Block Diagram
FBD Block
Operand
Type
Format
Description
COS tag
FBD_MATH_ADVANCED
tag
COS structure
FBD_MATH_ADVANCED Structure
Input Members
Data Type
Description
EnableIn
BOOL
Enable input. If false, the instruction does not execute and outputs are not updated.
Default is set.
Source
REAL
Input to the trigonometric instruction.
Output Members
Data Type
Description
EnableOut
BOOL
Indicates if the instruction executed without fault when it was enabled.
Dest
REAL
Result of the instruction.
FBD Function
Operand
Data Type
Description
Source
SINT
INT
DINT
LINT
USINT
UINT
UDINT
ULINT
REAL
LREAL
Value to convert to cosine.
Output Operand (Right Pin)
Data Type
Description
Dest
REAL
LREAL
Result of the function.
Operator Aspects
The COS operator can be used in various expressions. Similarly, the COS function is invoked in Structured Text statements. Both applications of COS return a floating point result containing the cosine of the Source. Depending on the context this value may then be type converted if appropriate.
Affects Math Status Flags
Conditional
Major/Minor Faults
None specific to this instruction. See Index Through Arrays for array-indexing faults.
Execution
Ladder Diagram
Condition/State
Action Taken
Prescan
N/A
Rung-condition-in is false
Set Rung-condition-out to Rung-condition-in.
Rung-condition-in is true
Set Rung-condition-out to Rung-condition-in.
Dest = cosine value of the Source.
Postscan
N/A
Function Block Diagram
FBD Block
Condition/State
Action Taken
Prescan
N/A
EnableIn is false
Set EnableOut to EnableIn.
EnableIn is true
Dest = cosine value of the Source.
If overflow occurs
Clear EnableOut to false
else
Set EnableOut to true.
Instruction first run
N/A
Instruction first scan
N/A
Postscan
N/A
FBD Function
Condition/State
Action Taken
Prescan
N/A
Normal Scan
Dest = cosine value of the Source.
Instruction first run
N/A
Instruction first scan
N/A
Postscan
N/A
Example
Ladder Diagram
COS_LD_ex_v31
Function Block Diagram
FBD Block
COS_example_FBDFunction
FBD Function
COS_FBD_ex_v31
Structured Text
REAL_dest := COS(REAL_src);
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal