Maximum Capture (MAXC)
The Maximum Capture (MAXC) instruction retains the maximum value of the input over time and allows the user to re-establish a maximum as needed.
Available Languages
Ladder Diagram
This instruction is not available in ladder diagram logic.
Function Block

Structured Text
MAXC(MAXC_tag);
Operands
Function Block
Operand | Type | Format | Description |
MAXC tag | MAXIMUM_CAPTURE | Structure | MAXC structure |
MAXIMUM_CAPTURE Structure
Input Parameter | Data Type | Description |
EnableIn | BOOL | Enable input. If cleared, the instruction does not execute and outputs are not updated.
Default is set. |
In | REAL | The analog signal input to the instruction.
Valid = any float
Default = 0.0 |
Reset | BOOL | Request to reset control algorithm. The instruction sets Out = ResetValue as long as Reset is set.
Default is cleared. |
ResetValue | REAL | The reset value for the instruction. The instruction sets Out = ResetValue as long as Reset is set.
Valid = any float
Default = 0.0 |
Output Parameter | Data Type | Description |
EnableOut | BOOL | Enable output. |
Out | REAL | The calculated output of the algorithm. |
Structured Text
Operand | Type | Format | Description |
MAXC tag | MAXIMUM_CAPTURE | Structure | MAXC structure |
See Structured Text Syntax for more information on the syntax of expressions within structured
text.
Description
The MAXC instruction executes this algorithm:
Condition | Action |
Reset is set | LastMaximum = Reset value Out = LastMaximum |
Reset is cleared | If In > LastMaximum then update LastMaximum.
Out = LastMaximum. |
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Common Attributes for
operand-related faults.
Execution
Function Block
Condition/State | Action Taken |
Prescan | EnableIn and EnableOut bits are cleared to false. |
Tag.EnableIn is false | EnableIn and EnableOut bits are cleared to false. |
Tag.EnableIn is true | EnableIn and EnableOut bits are set to true. The instruction executes. |
Instruction first run | N/A |
Instruction first scan | Set request to initialize the Maximum value with the current input. |
Postscan | EnableIn and EnableOut bits are cleared to false. |
Structured Text
In Structured Text, EnableIn is always True during a normal scan. If the instruction is in
the control path activated by the logic, it executes.
Condition/State | Action Taken |
Prescan | See Prescan in the Function Block table. |
Normal Execution | See Tag.EnableIn is true in the Function Block table. |
Postscan | See Postscan in the Function Block table. |
Examples
If Reset is set, the instruction sets Out=ResetValue. If Reset is cleared, the instruction sets Out=In when In> LastMaximum. Otherwise, the instruction sets Out= LastMaximum.
Function Block

Structured Text
MAXCTag.In := input_value;
MAXCTag.Reset := reset_input;
MAXCTag.ResetValue := reset_value;
MAXC(MAXCTag);
result := MAXCTag.Out;