Proportional Integral Derivative (PID)

The PID instruction controls a process variable such as flow, pressure, temperature, or level.
The PID instruction typically receives the process variable (PV) from an analog input module and modulates a control variable output (CV) on an analog output module in order to maintain the process variable at the desired setpoint.
The .EN bit indicates execution status. The .EN bit is set when the EnableIn transitions from false to true. The .EN bit is cleared when the EnableIn becomes false. The PID instruction does not use a .DN bit. The PID instruction executes every scan as long as the EnableIn is true.
Available Languages
Ladder Diagram
Structured Text
PID(PID,ProcessVariable,Tieback,ControlVariable,PIDMasterLoop,InHoldBit,InHoldValue);
Operands
There are data conversion rules for mixed data types within an instruction. See Data conversions.
Ladder Diagram
Operand
Type
Format
Description
PID
PID
structure
PID structure
Process variable
SINT
tag
Value you want to control
INT
DINT
REAL
Tieback
SINT
immediate
(optional)
INT
tag
DINT
Output of a hardware hand/auto station which is bypassing the output of the controller.
Enter 0 if you don’t want to use this parameter
REAL
Control variable
SINT
tag
Value which goes to the final control device (valve, damper, etc.)
INT
DINT
If you are using the deadband, the Control variable must be REAL or it will be forced to 0 when the error is within the deadband.
REAL
PID master loop
PID
Structure
Optional
PID tag for the master PID
If you are performing cascade control and this PID is a slave loop, enter the name of the master PID
Enter 0 if you do not want to use this parameter
Inhold bit
BOOL
tag
Optional
Current status of the inhold bit from a 1756 analog
Output channel to support bumpless restart
Inhold value
SINT
tag
Optional
INT
Data readback value from a 1756 analog output
DINT
Channel to support bumpless restart
REAL
Enter 0 if you don’t want to use this parameter
Setpoint
Display only
Current value of the setpoint
Process variable
Display only
Current value of the scaled Process_Variable
Output %
Display only
Current output percentage value
PID structure
Specify a unique PID structure for each PID instruction.
Mnemonic
Data Type
Description
.CTL
DINT
The .CTL member provides access to the status members (bits) in one, 32-bit word.
Bits 07-15 are set by the PID instruction.
See .CTL member.
.SP
REAL
setpoint
.KP
REAL
Independent - proportional gain (unitless)
Dependent - controller gain (unitless)
.KI
REAL
Independent - integral gain (1/sec)
Dependent - reset time (minutes per repeat)
.KD
REAL
Independent - derivative gain (seconds)
Dependent - rate time (minutes)
.BIAS
REAL
feedforward or bias %
.MAXS
REAL
maximum engineering unit scaling value
.MINS
REAL
minimum engineering unit scaling value
.DB
REAL
deadband engineering units
.SO
REAL
set output %
.MAXO
REAL
maximum output limit (% of output)
.MINO
REAL
minimum output limit (% of output)
.UPD
REAL
loop update time (seconds)
.PV
REAL
scaled PV value
.ERR
REAL
scaled error value
.OUT
REAL
output %
.PVH
REAL
process variable high alarm limit
.PVL
REAL
process variable low alarm limit
.DVP
REAL
positive deviation alarm limit
.DVN
REAL
negative deviation alarm limit
.PVDB
REAL
process variable alarm deadband
.DVDB
REAL
deviation alarm deadband
.MAXI
REAL
maximum PV value (unscaled input)
.MINI
REAL
minimum PV value (unscaled input)
.TIE
REAL
tieback value for manual control
.MAXCV
REAL
maximum CV value (corresponding to 100%)
.MINCV
REAL
minimum CV value (corresponding to 0%)
.MINITIE
REAL
minimum tieback value (corresponding to 100%)
.MAXTIE
REAL
maximum tieback value (corresponding to 0%)
.DATA[17]
REAL
The .DATA member stores:
  • .DATA[0] - integral accumulation
  • .DATA[1] - derivative smoothing temporary value
  • .DATA[2] - previous .PV value
  • .DATA[3] - previous .ERR value
  • .DATA[4] - previous valid .SP value
  • .DATA[5] - percent scaling constant
  • .DATA[6] - .PV scaling constant
  • .DATA[7] - derivative scaling constant
  • .DATA[8] - previous .KP value
  • .DATA[9] - previous .KI value
  • .DATA[10] - previous .KD value
  • .DATA[11] - dependend gain .KP
  • .DATA[12] - dependend gain .KI
  • .DATA[13] - dependend gain .KD
  • .DATA[14] - previous .CV value
  • .DATA[15] - .CV descaling constant
  • .DATA[16] - tieback descaling constant
The .CTL member
Bit
Number
Description
.EN
31
.CT
30
cascade type (0=slave; 1=master)
.CL
29
cascade loop (0=no; 1=yes)
.PVT
28
process variable tracking (0=no; 1=yes)
.DOE
27
derivative of (0=PV; 1=error)
.SWM
26
software mode (0=no-auto); 1=yes- sw manual)
.CA
25
control action (0=reverse (SP-PV); 1=direct (PV- SP))
.MO
24
station mode (0=automatic; 1=manual)
.PE
23
PID equation (0=independent; 1=dependent)
.NDF
22
derivative smoothing (0=no; 1=yes)
.NOBC
21
bias calculation (0=no; 1=yes)
.NOZC
20
zero crossing (0=no; 1=for deadband)
.INI
15
PID initialized (0=no; 1=yes)
.SPOR
14
setpoint out of range (0=no; 1=yes)
.OLL
13
CV is below minimum output value (0=no; 1=yes)
.OLH
12
CV is above maximum output value (0=no; 1=yes)
.EWD
11
error is within deadband (0=no; 1=yes)
.DVNA
10
error is alarmed low (0=no; 1=yes)
.DVPA
9
error is alarmed high (0=no; 1=yes)
.PVLA
8
PV is alarmed low (0=no; 1=yes)
.PVHA
7
PV is alarmed high (0=no; 1=yes)
Affects Math Status Flags
No
Major/Minor Faults
A minor fault will occur if:
Fault Type
Fault Code
UPD ≥ 0
4
35
setpoint out of range
4
36
See Common Attributes for operand-related faults.
Execution
Ladder Diagram
Condition/State
Action Taken
Bounds checked operands
Prescan
Set .EN to false
Initialize the pid structure
PID
Tag.EnableIn is false
Set .EN to false
PID
Tag.EnableIn is true
Set .EN to true
The instruction executes the PID loop
All operands
Postscan
Set .EN to false
PID
Provide Feedback