Rate Limiter (RLIM)

The Rate Limiter (RLIM) instruction limits the amount of change of a signal over time.
Available Languages
Ladder Diagram
This instruction is not available in ladder diagram logic.
Function Block
RLIM_FBD_avail_v31
Structured Text
RLIM(RLIM_tag);
Operands
Function Block
Operand
Type
Format
Description
RLIM tag
RATE_LIMITER
structure
RLIM structure
RATE_LIMITER Structure
Input Parameter
Data Type
Description
EnableIn
BOOL
Enable input. If false, the instruction does not execute and outputs are not updated.
Default is true.
In
REAL
The analog signal input to the instruction.
Valid = any float
Default = 0.0
IncRate
REAL
Maximum output increment rate in per-second units. If invalid, the instruction sets IncRate = 0.0 and sets the appropriate bit in Status.
Valid = any float Greater than or equal to 0.0
Default = 0.0
DecRate
REAL
Maximum output decrement rate in per-second units. If invalid, the instruction sets DecRate = 0.0 and sets the appropriate bit in Status.
Valid = any float Greater than or equal to 0.0
Default = 0.0
ByPass
BOOL
Request to bypass the algorithm. When true, Out = In.
Default is false.
TimingMode
DINT
Selects timing execution mode.
0 = Period mode
1 = oversample mode
2 = real time sampling mode
Valid = 0 to 2
Default = 0
OversampleDT
REAL
Execution time for oversample mode.
Valid = 0 to 4194.303 seconds
Default = 0
RTSTime
DINT
Module update period for real time sampling mode
Valid = 1 to 32,767ms
Default = 1
RTSTimeStamp
DINT
Module time stamp value for real time sampling mode.
Valid = 0 to 32,767ms
Default = 0
Output Parameter
Data Type
Description
EnableOut
BOOL
Indicates if instruction is enabled. Cleared to false if Out overflows.
Out
REAL
The calculated output of the algorithm.
DeltaT
REAL
Elapsed time between updates. This is the elapsed time in seconds used by the control algorithm to calculate the process output.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
IncRateInv (Status.1)
BOOL
IncRate < 0. The instruction uses 0.
DecRateInv (Status.2)
BOOL
DecRate < 0. The instruction uses 0.
TimingModeInv (Status.27)
BOOL
Invalid TimingMode value.
For more information about timing modes, see Function Block Attributes.
RTSMissed (Status.28)
BOOL
Only used in real time sampling mode. Set to true when
ABS(DeltaT – RTSTime) > 1 millisecond.
RTSTimeInv (Status.29)
BOOL
Invalid RTSTime value.
RTSTimeStampInv (Status.30)
BOOL
Invalid RTSTimeStamp value.
DeltaTInv (Status.31)
BOOL
Set to true in oversample mode if either DeltaT <= 0 or DeltaT > 4194.303.
Structured Text
Operand
Type
Format
Description
RLIM tag
RATE_LIMITER
structure
RLIM structure
See Structured Text Syntax for more information on the syntax of expressions within structured text.
Description
The RLIM instruction provides separate increment and decrement rates in per-second units. The ByPass input lets you stop rate limiting and pass the signal directly to the output.
Condition
Action
ByPass is true
Out
n
= In
n
Out
n-1
= In
n
ByPass is false and
DeltaT > 0
RLIM Bypass is false action
Affects Math Status Flags
No
Major/Minor Faults
A minor fault will occur if the feature is enabled and overflow is detected (Fault Type: 4, Fault Code: 4).
Execution
Function Block
Condition/State
Action Taken
Prescan
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is false
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is true
EnableIn and EnableOut bits are set to true
The instruction executes.
Instruction first run
N/A
Instruction first scan
Initialize Out with the value of In.
Postscan
EnableIn and EnableOut bits are cleared to false.
Structured Text
Condition/State
Action Taken
Prescan
See Prescan in the Function Block table.
Normal Execution
See Tag.EnableIn is true in the Function Block table.
Postscan
See Postscan in the Function Block table.
Example
Function Block
The RLIM instruction limits In by IncRate. If analog_input1 changes at a rate greater than the IncRate value, the instruction limits In. The instruction sets Out = rate limited value of In.
Structured Text
RLIM_01.In := analog_input1;
RLIM_01.IncRate := value;
RLIM(RLIM_01);
rate_limited := RLIM_01.Out;