High/Low Limit (HLL)

The High/Low Limit (HLL) instruction limits an analog input between two values. You can select high/low, high, or low limits.
Available Languages
Ladder Diagram
This instruction is not available in ladder diagram logic.
Function Block
HLL_FBD_avail_v31
Structured Text
HLL(HLL_tag);
Operands
Function Block
Operand
Type
Format
Description
HLL tag
HL_LIMIT
structure
HLL structure
HL_LIMIT Structure
Input Parameter
Data Type
Description
EnableIn
BOOL
Enable input. If false, the instruction does not execute and outputs are not updated.
Default is true.
In
REAL
The analog signal input to the instruction.
Valid = any float
Default = 0.0
HighLimit
REAL
The high limit for the Input. If SelectLimit = 0 and HighLimit Less than or equal to LowLimit, the instruction sets the appropriate bit in Status and sets Out = LowLimit.
Valid = HighLimit > LowLimit
Default = 0.0
LowLimit
REAL
The low limit for the Input. If SelectLimit = 0 and LowLimit Greater than or equal to HighLimit, the instruction sets the appropriate bit in Status and sets Out = LowLimit.
Valid = LowLimit < HighLimit
Default = 0.0
SelectLimit
DINT
Select limit input. This input has three settings:
0 = Use both limits
1= Use high limit
2 = Use low limit
If SelectLimit is invalid, the instruction assumes SelectLimit = 0 and sets the appropriate bit in Status.
Valid = 0 to 2
Default = 0
Output Parameter
Data Type
Description
EnableOut
BOOL
Indicates if instruction is enabled. Cleared to false if Out overflows.
Out
REAL
The calculated output of the algorithm.
HighAlarm
BOOL
The high alarm indicator. Set to true when In Greater than or equal to HighLimit. The HighAlarm is disabled when SelectLimit is set to 2.
LowAlarm
BOOL
The low alarm indicator. Set to true when In Less than or equal to LowLimit. The LowAlarm is disabled when SelectLimit is set to 1.
Status
DINT
Status of the function block.
InstructFault (Status.0)
BOOL
The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred.
LimitsInv (Status.1)
BOOL
HighLimit Less than or equal to LowLimit.
SelectLimitInv (Status.2)
BOOL
The value of SelectLimit is not a 0, 1, or 2.
Structured Text
Operand
Type
Format
Description
HLL tag
HL_LIMIT
structure
HLL structure
See Structured Text Syntax for more information on the syntax of expressions within structured text.
Description
The HLL instruction determines the value of the Out using these rules:
Selection
Condition
Action
SelectLimit = 0
(use high and low limits)
In < HighLimit and
In > LowLimit
Out = In
In Greater than or equal to HighLimit
Out = HighLimit
In Less than or equal to LowLimit
Out = LowLimit
HighLimit Less than or equal to LowLimit
Out = LowLimit
SelectLimit = 1
(use high limit only)
In < HighLimit
Out = In
InGreater than or equal toHighLimit
Out = HighLimit
SelectLimit = 2
(use low limit only)
In > LowLimit
Out = In
In Less than or equal to LowLimit
Out = LowLimit
Affects Math Status Flags
No
Major/Minor Faults
A minor fault will occur if the feature is enabled and overflow is detected (Fault Type: 4, Fault Code: 4).
Execution
Function Block
Condition/State
Action Taken
Prescan
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is false
EnableIn and EnableOut bits are cleared to false.
Tag.EnableIn is true
EnableIn and EnableOut bits are set to true.
The instruction executes.
Instruction first run
N/A
Instruction first scan
N/A
Postscan
EnableIn and EnableOut bits are cleared to false.
Structured Text
Condition/State
Action Taken
Prescan
See Prescan in the Function Block table.
Normal Execution
See Tag.EnableIn is true in the Function Block table.
Postscan
See Postscan in the Function Block table.
Example
This HLL instruction limits In between two values and sets HighAlarm or LowAlarm, if needed when In is outside the limits. The instruction sets Out = limited value of In.
Function Block
HLL_FBD_ex_v31
Structured Text
HLL_01.In := value;
HLL_01.HighLimit := high_limit;
HLL_01.LowLimit := low_limit;
HLL(HLL_01);
limited_value := HLL_01.Out;
high_alarm := HLL_01.HighAlarm;
low_alarm := HLL_01.LowAlarm;