Four Sensor Bi-Directional Muting (FSBM)

This instruction applies to the
safety controllers
.
The Four Sensor Bi-Directional Muting (FSBM) instruction provides a temporary, automatic disabling of the protective function of a light curtain, which allows material to be transported through the light curtain sensing field without stopping the machine. Muting sensors differentiate between materials and personnel and must act together along with the light curtain, in a specific switching sequence when the appropriate material passes the sensing field.
The Direction input sets the expected direction from which the material passes through the sensing field. Once this direction is established, and providing the proper sequencing of the sensors and light curtain is maintained, bidirectional movement of the material is permitted.
Available Languages
Ladder Diagram
FSBM_LD_avail_v31
Function Block
This instruction is not available in function block.
Structured Text
This instruction is not available in structured text.
Four Sensor Bi-Directional Muting Application
Four-Sensor Bi-Directional Muting uses four muting sensors arranged sequentially before and after the light curtain’s center of the protected opening.
FSBM 4-sensor bi-dir muting application
WARNING: The muting sensors must be arranged so a person cannot activate the muting sensors in the same switching sequence as the material and enter the area when a hazardous condition exists. Sensor setup must take into account material size, shape, and speed. Additional guarding may also be necessary.
Specific guarding requirements should be identified through a hazard or risk assessment of the application.
Operands
IMPORTANT: Unexpected operation, including controller assert or a Major Non-Recoverable Fault, can occur if:
  • Backing tag members are written to.
  • Backing tags are shared by multiple instruction invocations.
  • Backing tag members are passed as parameters to an instruction controlled by the same backing tag.
  • The backing tag
    .EnableIn
    member is referenced anywhere in the program.
    .EnableIn
    is a parameter that represents rung state into an instruction and is only intended for internal use.
    For examples of these incorrect backing tag usages, see Backing tag usages that can cause unexpected operation.
WARNING: The FSBM structure contains internal state information.
WARNING:
If changing instruction configuration operands while in Run mode, accept the pending edits and do one of the following for the changes to take effect:
  • Change the controller mode to Program and then back to Run.
  • Change the rung in condition to false and then back to true.
Either of these actions will reset the instruction state machine and turn off all instruction outputs. Manual restarts may be required after this modification, depending on the application logic.
The following table provides the operands that are used to configure the instruction.
Operand
Data Type
Format
Description
FSBM
MUTING_FOUR_SENSOR_BDIR
tag
This parameter is a backing tag. As such, it maintains important execution information for each usage of this instruction.
Restart Type
BOOL
list item
This input configures O1 (Output 1) for either manual or automatic restart.
MANUAL (0)
A transition of the reset input from OFF (0) to ON (1), while all of the Output 1 enabling conditions are met, is required to energize Output 1.
AUTOMATIC (1)
Output 1 is energized 50 ms when all of the enabling conditions are met.
TIP: Only use Automatic Restart in application situations where it is determined that no unsafe conditions will occur from its use.
S1-S2 Time
DINT
immediate
The maximum amount of time allowed between Sensor 1 being blocked and Sensor 2 being blocked before a fault occurs.
The valid range is 5 through 180,000 ms. Setting this input to 0 disables the S1-S2 timer.
S2-LC Time
DINT
immediate
The maximum amount of time allowed between Sensor 2 being blocked and the Light Curtain being cleared before a fault occurs.
The valid range is 5 through 180,000 ms. Setting this input to 0 disables the S2-LC timer.
LC-S3 Time
DINT
immediate
The maximum amount of time allowed between Sensor 3 being blocked and the Light Curtain being blocked before a fault occurs.
The valid range is 5 through 180,000 ms. Setting this input to 0 disables the LC-S3 timer.
S3-S4 Time
DINT
immediate
The maximum amount of time allowed between Sensor 3 being blocked and Sensor 4 being blocked before a fault occurs.
The valid range is 5 through 180,000 ms. Setting this input to 0 disables the S3-S4 timer.
Maximum Mute Time
DINT
immediate
The maximum amount of time during which the instruction lets the protective function of the light curtain be disabled before generating a fault.
The valid range is 0 through 3600 s. Setting this input to 0 disables the Maximum Mute timer.
Maximum Override Time
DINT
immediate
The maximum amount of time that the instruction lets the override feature energize the Output 1 output.
The valid range is 0 through 30 s. Setting this input to 0 disables the Maximum Override timer.
The following table explains the instruction inputs.
Operand
Data Type
Format
Description
Direction
BOOL
immediate
tag
This input specifies the sequencing direction.
ON (1): Forward. The muting sequence begins with the blocking of Sensor 1.
OFF (0): Reverse. The muting sequence begins with the blocking of Sensor 4.
Light Curtain
BOOL
tag
An input channel with OFF (0) as its safe state, this input represents the current state of the physical light curtain. This input must be properly conditioned. Use the Dual Channel Input Stop instruction controlling a light curtain to accomplish this.
ON (1): The light curtain is clear.
OFF (0): The light curtain is blocked.
Sensor 1
BOOL
tag
One of four muting sensors. When material is moving in the forward direction, it is the first sensor to be blocked and cleared. When material is moving in the reverse direction, it is the fourth to be blocked and cleared.
ON (1): Sensor 1 is clear.
OFF (0): Sensor 1 is blocked.
Sensor 2
BOOL
tag
One of four muting sensors. When material is moving in the forward direction, it is the second sensor to be blocked and cleared. When material is moving in the reverse direction, it is third to be blocked and cleared.
ON (1): Sensor 2 is clear.
OFF (0): Sensor 2 is blocked.
Sensor 3
BOOL
tag
One of four muting sensors. When material is moving in the forward direction, it is the third sensor to be blocked and cleared. When material is moving in the reverse direction, it is second to be blocked and cleared.
ON (1): Sensor 3 is clear.
OFF (0): Sensor 3 is blocked.
Sensor 4
BOOL
tag
One of four muting sensors. When material is moving in the forward direction, it is the fourth sensor to be blocked and cleared. When material is moving in the reverse direction, it is first to be blocked and cleared.
ON (1): Sensor 4 is clear.
OFF (0): Sensor 4 is blocked.
Enable Mute
BOOL
immediate
tag
This input allows the protective function of the light curtain to be disabled (muted) when the correct muting sequence occurs.
ON (1): The protective function of the light curtain is disabled when the correct muting sequence occurs.
OFF (0): The protective function of the light curtain is always enabled.
Override
BOOL
tag
This input allows a temporary bypass of the muting instruction’s function. Output 1 is energized regardless of the status of the Input Status input or the existence of faults.
OFF (0): Output 1 is disabled.
OFF (0) -> ON (1): Output 1 is energized regardless of the status of the Input Status input or the existence of faults. Output 1 remains energized while the Override input remains ON (1) or until the Maximum Override timer expires.
TIP: Activation of the override function requires the use of a hold-to-run device where the operator can see the point of hazard, that is, the light curtain sensing field.
Input Status
BOOL
immediate
tag
If the instruction inputs are from a safety I/O module, this is the status from the I/O module (Connection Status or Combined Status). If the instruction inputs are derived from internal logic, it is the application programmer’s responsibility to determine the conditions.
ON (1): The inputs to this instruction are valid.
OFF (0): The inputs to this instruction are invalid.
Muting Lamp Status
BOOL
immediate
tag
This input represents the status of the muting lamp.
ON (1): The muting lamp is operating properly. The light curtain’s protective function is disabled (muted) after the correct muting sequence is followed.
OFF (0): The muting lamp is defective or missing. The light curtain’s protective function is always enabled.
Reset
1
BOOL
tag
This input clears instruction and circuit faults provided the fault condition is not present.
OFF (0) -> ON (1): The FP (Fault Present) and Fault Code outputs are reset.
Output 1 is energized when the Restart Type is manual. Output 1 is not energized at the same time faults are cleared.
1
Some safety standards require monitoring the transition of the reset input. When the reset is used to reset a safety function, additional logic may be required to verify a transition of the reset input from High-to-Low or Low-to-High.
The following table explains the instruction outputs.
Operand
Data Type
Description
Output 1 (01)
BOOL
ON (1): The light curtain sensing field is not obstructed, the light curtain is being muted, or the light curtain is being overridden.
OFF (0): The light-curtain sensing field is obstructed or the muting sensors sequence is incorrect.
Muting Lamp (ML)
BOOL
ON (1): The light curtain’s protective function is disabled.
OFF (0): The light curtain’s protective function is enabled.
Clear Area (CA)
BOOL
This status output indicates when the light-curtain sensing field and all muting sensors must be cleared (ON) before processing can continue.
ON (1): The light curtain sensing field must be cleared.
OFF (0): Normal operation
Diagnostic Code
DINT
This output indicates the diagnostic status of the instruction. See the Diagnostic Codes for a list of diagnostic codes. This operand is not safety-related.
Fault Code
DINT
This output indicates the type of fault that occurred. See the FSBM General Fault Codes for the list of fault codes. This operand is not safety-related.
Fault Present (FP)
BOOL
ON (1): A fault is present in the instruction.
OFF (0): The instruction is operating normally.
IMPORTANT: Do not write to any instruction output tag under any circumstances.
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Index Through Arrays for array-indexing faults.
Execution
Condition/State
Action Taken
Prescan
Same as Rung-condition-in is false.
Rung-condition-in is false
The .O1, .ML, .CA and .FP are cleared to false.
Rung-condition-in is true
The instruction executes as described in the Normal Operation section.
Postscan
Same as Rung-condition-in is false.
Operation
Normal Operation
One forward direction and one reverse direction sequence of muting sensor and light-curtain input transitions let the protective function of the light curtain be disabled (muted). Both sequences start with the four muting sensors and the light curtain in their ON (1) state. This indicates that the light-curtain sensing field is clear of all personnel and material.
At (A), when Sensors 1 through 4 and the Light Curtain are clear, the Output 1 output is energized when the Reset input turns ON (1). At (B), material blocks Sensor 1, starting the S1-S2 timer. At (C), the material blocks Sensor 2, stopping the S1-S2 timer. The S2-LC and Maximum Mute timers start. The Muting Lamp turns ON (1), indicating that muting is enabled. At (D), the material blocks the Light Curtain, stopping the S2-LC timer and starting the LC-S3 timer. At (E), the material blocks Sensor 3, stopping the LC-S3 timer and starting the S3-S4 timer. At (F), the material blocks Sensor 4, stopping the S3-S4 timer. The material is blocking all of the Sensors and the Light Curtain. From (G) through (K), the material clears the sensors and the Light Curtain in the same order in which they were blocked, starting and stopping the timers, until the material clears all of the sensors and the Light Curtain.
The following diagrams shows the sequence as described for the forward and reverse directions.
Normal Operation, Forward Direction
Four Sensor Bidirectional Muting (FSBM) (85)
Normal Operation, Reverse Direction
FSBM_norm oper, reverse
Invalid Sequence
Any input sequence other than the normal operation sequence results in Output 1 being de-energized.
At (A), Output 1 is energized just as in a normal sequence of operation. At (B), the material blocks Sensor 1, starting the S1-S2 timer. At (C), the material simultaneously blocks Sensor 2 and the Light Curtain, stopping the S1-S2 timer. Output 1 is de-energized and the Clear Area and Fault Present outputs turn ON (1). The override feature can be used to clear the material from the sensing field and turn the Clear Area output OFF (0).
FSBM_invalid sequence
Tolerated Sequence
The Four-sensor Bidirectional Muting (FSBM) instruction tolerates application dynamics that might cause an input to oscillate due to over-travel or load vibration.
At (A), Output 1 is energized just as in a normal sequence of operation. At (B), Sensor 1 turns OFF (0), starting the S1-S2 timer. At (C), Sensor 1 turns ON, stopping the S1-S2 timer. At (D), the material completely blocks Sensor 1, turning it OFF (0) and the normal muting sequence continues. A sensor may glitch, as illustrated from (B) to (C), as a result of over-travel or load vibration. As long as the final input sequence is valid, the instruction lets the muting function occur.
FSBM_Tolerated Sequence
Dangerous Portion of Cycle
The Enable Mute input enables or disables the protective function of the light curtain. When the Enable Mute input is OFF (0), the protective function of the light curtain is enabled and material may not pass through the light curtain sensing field.
At (A), Output 1 is energized just as in a normal sequence of operation. At (B), the material blocks Sensor 1, starting the S1-S2 timer. At (C), the material blocks Sensor 2, stopping the S1-S2 timer and starting the S2-LC timer. Because the Enable Mute input is OFF(0), muting is disabled and the Muting Lamp output remains OFF (0). The material blocks the Light Curtain at (D), stopping the S2-LC timer. Output 1 is de-energized because the Enable Mute input is OFF (0)
If the application does not have parts of its cycle where it is unacceptable for material to pass through the light curtain, disable this feature by setting the Enable Mute input to a constant value of ON (1).
FSBM Dangerous portion of cyclE
Override Operation
The override feature enables an operator to manually energize Output 1 so that material can be cleared from the light curtain sensing field.
WARNING: Only use the Override function may be used only with a hold-to-run device where the operator can see the point of hazard, that is, the light curtain sensing field.
At (A), the Override input turns ON (1). Output 1 is energized and the Maximum Override timer starts. At (B), the material clears Sensor 3 and Sensor 4 and the Clear Area output turns OFF (0). At (C), the Override input turns OFF (0) within the Maximum Override time period. Output 1 is de-energized and the Maximum Override timer stops.
FSBM_override operation
False Rung State Behavior
When the instruction is executed on a false rung, all instruction outputs are de-energized.
Fault Codes
The fault codes are listed in hexadecimal format followed by decimal format.
General Fault Codes
Fault Code
Description
Corrective Action
00
No fault.
None.
16#20
32
The Input Status input went from ON (1) to OFF (0) while the instruction was executing.
  • Check the I/O module connection or the logic used to source input status.
  • Reset the fault.
Illegal Input Faults
Fault Code
Description
S1
S2
LC
S3
S4
16#9200
37376
The Light Curtain, Sensors 1, 2, and 4 are blocked, while Sensor 3 is clear.
0
0
0
1
0
16#9201
37377
Sensors 1, 2, 3, and 4 are blocked and the Light Curtain is clear.
0
0
1
0
0
16#9202
37378
Sensors 1, 2, and 3 are blocked and the Light Curtain and Sensor 4 are clear.
0
0
1
0
1
16#9203
37379
Sensors 1, 2, and 4 are blocked and the Light Curtain and Sensor 3 are clear.
0
0
1
1
0
16#9204
37380
Sensors 1, 3, and 4 and the Light Curtain are blocked and Sensor 2 is clear.
0
1
0
0
0
16#9205
37381
Sensors 1, 3, and the Light Curtain are blocked and sensors 2 and 4 are clear.
0
1
0
0
1
16#9206
37382
Sensors 1, 4 and the Light Curtain are blocked and Sensors 2 and 3 are clear.
0
1
0
1
0
916#207
37383
Sensor 1 and the Light Curtain are blocked and Sensors 2, 3, and 4 are clear.
0
1
0
1
1
16#9208
37384
Sensor 2 and the Light Curtain are blocked and Sensors 1, 3, and 4 are clear.
0
1
1
0
0
16#9209
37385
Sensors 1 and 3 are blocked and Sensors 2 and 4 and the Light Curtain are clear.
0
1
1
0
1
16#920A
37386
Sensors 1 and 4 are blocked and Sensors 2 and 3 and the Light Curtain are clear.
0
1
1
1
0
16#920B
37387
Sensors 2 and 3 and the Light Curtain are blocked and Sensors 1 and 4 are clear.
1
0
0
0
1
16#920C
37388
Sensors 2 and 4 and the Light Curtain are blocked and Sensors 1 and 3 are clear.
1
0
0
1
0
16#920D
37389
Sensor 2 and the Light Curtain are blocked and Sensors 1, 3, and 4 are clear.
1
0
0
1
1
16#920E
37390
Sensors 2, 3, and 4 are blocked and Sensor 1 and the Light Curtain are clear.
1
0
1
0
0
16#920F
37391
Sensors 2 and 3 are blocked and Sensors 1 and 4 and the Light Curtain are clear.
1
0
1
0
1
16#9210
37392
Sensors 2 and 4 are blocked and Sensors 1 and 3 and the Light Curtain are clear.
1
0
1
1
0
16#9211
37393
Sensor 2 is blocked and Sensors 1, 3, and 4 and the Light Curtain are clear.
1
0
1
1
1
16#9212
37394
Sensor 3 and the Light Curtain are blocked and Sensors 1, 2, and 4 are clear.
1
1
0
0
1
16#9213
37395
Sensor 4 and the Light Curtain are blocked and Sensors 1, 2, and 3 are clear.
1
1
0
1
0
16#9214
37396
The Light Curtain is blocked and Sensors 1, 2, 3, and 4 are clear.
1
1
0
1
1
16#9215
37397
Sensor 3 is blocked and Sensors 1, 2, and 4 and the Light Curtain are clear.
1
1
1
0
1
To recover from an illegal input fault:
  1. Check that the sensors and the light curtain are properly aligned, are applied to the appropriate instruction inputs, and are not being improperly blocked.
  2. Reset the fault.
Normal Muting Sequences
FSBM_normal muting sequences
An illegal muting sequence was detected in step 0 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9100
37120
Four Sensor Bidirectional Muting (FSBM) (92)
16#9101
37121
Four Sensor Bidirectional Muting (FSBM) (93)
16#9102
37122
Four Sensor Bidirectional Muting (FSBM) (94)
16#9103
37123
Four Sensor Bidirectional Muting (FSBM) (95)
16#9104
37124
Four Sensor Bidirectional Muting (FSBM) (96)
16#9105
37125
Four Sensor Bidirectional Muting (FSBM) (97)
16#9106
37126
Four Sensor Bidirectional Muting (FSBM) (17)
An illegal muting sequence was detected in step 1 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9110
37136
Four Sensor Bidirectional Muting (FSBM) (98)
16#9111
37137
Four Sensor Bidirectional Muting (FSBM) (99)
16#9112
37138
Four Sensor Bidirectional Muting (FSBM) (100)
16#9113
37139
Four Sensor Bidirectional Muting (FSBM) (101)
16#9114
37140
Four Sensor Bidirectional Muting (FSBM) (102)
16#9115
37141
Four Sensor Bidirectional Muting (FSBM) (103)
16#9116
37142
Four Sensor Bidirectional Muting (FSBM) (104)
An illegal muting sequence was detected in step 2 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9120
37152
Four Sensor Bidirectional Muting (FSBM) (105)
16#9121
37153
Four Sensor Bidirectional Muting (FSBM) (106)
16#9122
37154
Four Sensor Bidirectional Muting (FSBM) (107)
16#9123
37155
Four Sensor Bidirectional Muting (FSBM) (108)
16#9124
37156
Four Sensor Bidirectional Muting (FSBM) (109)
16#9125
37157
Four Sensor Bidirectional Muting (FSBM) (110)
16#9126
37158
Four Sensor Bidirectional Muting (FSBM) (111)
An illegal muting sequence was detected in step 3 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9130
37168
Four Sensor Bidirectional Muting (FSBM) (112)
16#9131
37169
Four Sensor Bidirectional Muting (FSBM) (113)
16#9132
37170
Four Sensor Bidirectional Muting (FSBM) (114)
16#9133
37171
Four Sensor Bidirectional Muting (FSBM) (115)
16#9134
37172
Four Sensor Bidirectional Muting (FSBM) (116)
16#9135
37173
Four Sensor Bidirectional Muting (FSBM) (117)
16#9136
37174
Four Sensor Bidirectional Muting (FSBM) (118)
An illegal muting sequence was detected in step 4 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9140
37184
Four Sensor Bidirectional Muting (FSBM) (119)
16#9141
37185
Four Sensor Bidirectional Muting (FSBM) (120)
16#9142
37186
Four Sensor Bidirectional Muting (FSBM) (121)
16#9143
37187
Four Sensor Bidirectional Muting (FSBM) (122)
16#9144
37188
Four Sensor Bidirectional Muting (FSBM) (123)
16#9145
37189
Four Sensor Bidirectional Muting (FSBM) (124)
16#9146
37190
Four Sensor Bidirectional Muting (FSBM) (125)
An illegal muting sequence was detected in step 5 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9150
37200
Four Sensor Bidirectional Muting (FSBM) (126)
16#9151
37201
Four Sensor Bidirectional Muting (FSBM) (127)
16#9152
37202
Four Sensor Bidirectional Muting (FSBM) (128)
16#9153
37203
Four Sensor Bidirectional Muting (FSBM) (129)
16#9154
37204
Four Sensor Bidirectional Muting (FSBM) (130)
16#9155
37205
Four Sensor Bidirectional Muting (FSBM) (131)
16#9156
37206
Four Sensor Bidirectional Muting (FSBM) (132)
An illegal muting sequence was detected in step 6 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9160
37216
Four Sensor Bidirectional Muting (FSBM) (133)
16#9161
37217
Four Sensor Bidirectional Muting (FSBM) (134)
16#9162
37218
Four Sensor Bidirectional Muting (FSBM) (135)
16#9163
37219
Four Sensor Bidirectional Muting (FSBM) (136)
16#9164
37220
Four Sensor Bidirectional Muting (FSBM) (137)
16#9165
37221
Four Sensor Bidirectional Muting (FSBM) (138)
16#9166
37222
Four Sensor Bidirectional Muting (FSBM) (139)
An illegal muting sequence was detected in step 7 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9170
37232
Four Sensor Bidirectional Muting (FSBM) (140)
16#9171
37233
Four Sensor Bidirectional Muting (FSBM) (141)
16#9172
37234
Four Sensor Bidirectional Muting (FSBM) (142)
16#9173
37235
Four Sensor Bidirectional Muting (FSBM) (143)
16#9174
37236
Four Sensor Bidirectional Muting (FSBM) (144)
16#9175
37237
Four Sensor Bidirectional Muting (FSBM) (145)
16#9176
37238
Four Sensor Bidirectional Muting (FSBM) (146)
An illegal muting sequence was detected in step 8 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9180
37248
Four Sensor Bidirectional Muting (FSBM) (147)
16#9181
37249
Four Sensor Bidirectional Muting (FSBM) (148)
16#9182
37250
Four Sensor Bidirectional Muting (FSBM) (149)
16#9183
37251
Four Sensor Bidirectional Muting (FSBM) (150)
16#9184
37252
Four Sensor Bidirectional Muting (FSBM) (151)
16#9185
37253
Four Sensor Bidirectional Muting (FSBM) (152)
16#9186
37254
Four Sensor Bidirectional Muting (FSBM) (153)
An illegal muting sequence was detected in step 9 when the Sensors and the Light Curtain transitioned to one of the following invalid sequence states.
Fault Code
Sequence
Fault Code
Sequence
Fault Code
Sequence
16#9190
37264
Four Sensor Bidirectional Muting (FSBM) (154)
16#9191
37265
Four Sensor Bidirectional Muting (FSBM) (155)
16#9192
37266
Four Sensor Bidirectional Muting (FSBM) (156)
16#9193
37267
Four Sensor Bidirectional Muting (FSBM) (157)
16#9194
37268
Four Sensor Bidirectional Muting (FSBM) (158)
16#9195
37269
Four Sensor Bidirectional Muting (FSBM) (159)
16#9196
37270
Four Sensor Bidirectional Muting (FSBM) (160)
An illegal muting sequence was detected when Sensor 1 or Sensor 4 transitioned to one of the following invalid sequence states. The first sensor blocked does not correspond to the value of the Direction input.
Fault Code
Sequence
Fault Code
Sequence
16#91A1
37281
Four Sensor Bidirectional Muting (FSBM) (161)
Direction = 1 (forward)
16#91A0
37280
Four Sensor Bidirectional Muting (FSBM) (162)
Direction = 0 (Reverse)
To recover from invalid sequence faults 16#9100…16#9196, check the alignment of the sensors with regard to the material being moved and the system timing and then reset the fault.
To recover from invalid sequence faults 16#91A0 and 16#91A1, check the value of the Direction input operand with respect to the movement of the material and reset the fault.
Correcting Invalid Sequence Faults
Fault Code
Description
Corrective Action
16#9000
36864
The Light Curtain was muted for longer than the configured Maximum Mute Time.
The Maximum Mute Time operand is set too short or there is an anomaly with the sensors.
16#9010
36880
Too much time elapsed between Sensor 1 and Sensor 2 being blocked.
The S1-S2 Time operand may be set too short or there may be a problem with Sensor 2 (forward direction) or Sensor 1 (reverse direction).
16#9011
38881
Too much time elapsed between Sensor 2 and the Light Curtain being blocked.
The S2-LC Time operand may be set too short or there may be a problem with the Light Curtain (forward direction) or Sensor 2 (reverse direction).
16#9012
36882
Too much time elapsed between the Light Curtain and Sensor 3 being cleared.
The LC-S3 Time operand may be set too short or there may be a problem with Sensor 3 (forward direction) or the Light Curtain (reverse direction).
16#9013
36883
Too much time elapsed between Sensor 3 and Sensor 4 being cleared.
The S3-S4 Time operand may be set to short or there may be a problem with Sensor 4 (forward direction) or Sensor 3 (reverse direction).
Diagnostic Codes and Corrective Actions
The diagnostic codes are listed in hexadecimal format followed by decimal format.
Diagnostic Code
Description
Corrective Action
00
No fault.
None
16#01
1
The Muting Lamp Status input is OFF (0).
Check the muting lamp and replace it, if necessary.
If a muting lamp is not required, set the Muting Lamp Status input to ON (1).
16#05
5
The Reset input is held ON (1)
Set the Reset input to OFF (0).
16#20
32
The Input Status input was OFF (0) when the instruction started.
Check the I/O module connection or the logic used to source input status.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal