Reset SFC (SFR)

The SFR instruction resets the execution of an SFC routine at a specified step.
Available Languages
Ladder Diagram
SFR_LD_avail_v31
Function Block
This instruction is not available in function block.
Structured Text
SFR(SFCRoutineName,StepName);
Operands
Ladder Diagram
Operand
Type
Format
Description
SFCRoutineName
ROUTINE
name
SFC routine to reset
StepName
SFC_STEP
tag
Target step where to resume execution
Structured Text
Operand
Type
Format
Description
SFCRoutineName
ROUTINE
name
SFC routine to reset
StepName
SFC_STEP
tag
Target step where to resume execution
See Structured Text Syntax for more information on the syntax of expressions within structured text.
Description
When the SFR instruction is enabled:
  • In the specified SFC routine, all stored actions stop executing (reset).
  • The SFC begins executing at the specified step.
  • If the target step is 0, the chart will be reset to is initial step.
The Logix implementation of the SFR instruction differs from that in the
PLC-5
controller. In the
PLC-5
controller, the SFR executes when the rung condition is true. After reset, the SFC would remain paused until the rung containing the SFR became false. This allowed the execution following a reset to be delayed. This pause/un-pause feature of the
PLC-5
SFR instruction was decoupled from the rung condition and moved into the SFP instruction.
Affects Math Status Flags
No
Fault Conditions
A major fault will occur if:
Fault Type
Fault Code
The routine type is not an SFC routine
4
85
Specified target step does not exist in the SFC routine
4
89
See Common Attributes for operand-related faults.
Execution
Ladder Diagram
Condition/State
Action Taken
Prescan
N/A
Rung-condition-inis false
N/A
Rung-condition-in is true
The instruction reset the specified SFC routine execution to a particular step.
Postscan
N/A
Structured Text
Condition/State
Action Taken
Prescan
N/A
Normal execution
The instruction reset the specified SFC routine execution to a particular step.
Postscan
N/A
Example
Ladder Diagram
SFR_LD_ex_v31