Scale (SCL)
The Scale (SCL) instruction converts an unscaled input value to a floating point value in engineering units.
Available Languages
Ladder Diagram
This instruction is not available in ladder diagram logic.
Function Block

Structured Text
SCL(SCL_tag)
Operands
Function Block
Operand | Type | Format | Description |
SCL tag | SCALE | Structure | SCL structure |
Structured Text
Operand | Type | Format | Description |
SCL tag | SCALE | Structure | SCL structure |
See
Structured Text Syntax
for more information on the syntax of expressions within structured text.SCALE Structure
Input Parameter | Data Type | Description |
EnableIn | BOOL | Enable input. If false, the instruction does not execute and outputs are not updated.
Default is true. |
In | REAL | The analog signal input.
Valid = any float
Default = 0.0 |
InRawMax | REAL | The maximum value attainable by the input to the instruction. If InRawMax InRawMin, the instruction sets the appropriate bit in Status and stops updating the output.
Valid = InRawMax > InRawMin
Default = 0.0 |
InRawMin | REAL | The minimum value attainable by the input to the instruction. If InRawMin InRawMax, the instruction sets the appropriate bit in Status and stops updating the output.
Valid = InRawMin < InRawMax
Default = 0.0 |
InEUMax | REAL | The scaled value of the input corresponding to InRawMax.
Valid = any real value
Default = 0.0 |
InEUMin | REAL | The scaled value of the input corresponding to InRawMin.
Valid = any real value
Default = 0.0 |
Limiting | BOOL | Limiting selector. If true, Out is limited to between InEUMin and InEUMax.
Default is false. |
Output Parameter | Data Type | Description |
EnableOut | BOOL | Indicates if instruction is enabled. Cleared to false if Out overflows. |
Out | REAL | The output that represents scaled value of the analog input.
Valid = any real value
Default = InEUMin |
MaxAlarm | BOOL | The above maximum input alarm indicator. This value is set to true when In> InRawMax. |
MinAlarm | BOOL | The below minimum input alarm indicator. This value is set to true when In < InRawMin. |
Status | DINT | Status of the function block. |
InstructFault (Status.0) | BOOL | The instruction detected one of the following execution errors. This is not a minor or major controller error. Check the remaining status bits to determine what occurred. |
InRawRangeInv (Status.1) | BOOL | InRawMin InRawMax. |
Description
Use the SCL instruction with analog input modules that do not support scaling to a full resolution floating point value.
For example, the 1771-IFE module is a 12-bit analog input module that supports scaling only in integer values. If you use a 1771-IFE module to read a flow of 0-100 gallons per minute (gpm), you typically do not scale the module from 0-100 because that limits the resolution of the module. Instead, use the SCL instruction and configure the module to return an unscaled (0-4095) value, which the SCL instruction converts to 0-100 gpm (floating point) without a loss of resolution. This scaled value could then be used as an input to other instructions.
The SCL instruction uses this algorithm to convert unscaled input into a scaled value:

Alarming
Once the instruction calculates Out, the MaxAlarm and MinAlarm are determined as follows:

Limiting
Limiting is performed on Out when Limiting is set. The instruction sets Out = InEUMax when In > InRawMax. The instruction sets Out = InEUMin when In < InRawMin.

Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. See Common Attributes for operand-related faults.
Execution
Function Block
Condition/State | Action Taken |
Prescan | EnableIn and EnableOut bits are cleared to false. |
Tag.EnableIn is false | EnableIn and EnableOut bits are cleared to false. |
Tag.EnableIn is true | EnableIn and EnableOut bits are set to true The instruction executes. |
Instruction first run | N/A |
Instruction first scan | N/A |
Postscan | EnableIn and EnableOut bits are cleared to false. |
Structured Text
Condition/State | Action Taken |
Prescan | See Prescan in the Function Block table. |
Normal Execution | See Tag.EnableIn is true in the Function Block table. |
Postscan | See Postscan in the Function Block table. |
Example
The SCL instruction is typically used with analog input modules that do not support on-board scaling to floating point engineering units. In this example, the SCL instruction scales an analog input from a 1771-IFE module. The instruction places the result in Out, which is used by an ALM instruction.
Function Block

Structured Text
SCL_01.In := Input0From1771IFE;
SCL(SCL_01);
ALM_01.In := SCL_01.Out;
ALM(ALM_01);
Provide Feedback
InRawMin, the instruction sets the appropriate bit in Status and stops updating the output.
InRawMax, the instruction sets the appropriate bit in Status and stops updating the output.