Move (MOVE)
The MOVE instruction moves a copy of the Source to the Dest. The Source remains
unchanged.
TIP:
In Logix Designer version 36, the mnemonic for this instruction changed
from MOV to MOVE.
Available Languages
Ladder Diagram

Function Block
This instruction is not available in function block.
Structured Text
This instruction is not available in structured text.
TIP:
Use an assignment ":=" with an expression to achieve the same result. Refer
to Structured Text Syntax for more information on the syntax of
expressions and assignments within structured text.
Operands
IMPORTANT:
Unexpected operation may occur if:
- Output tag operands are overwritten.
- Members of a structure operand are overwritten.
- Except when specified, structure operands are shared by multiple instructions.
There are data conversion rules for mixing numeric data types within an instruction. See
Data Conversions.
Ladder Diagram
Numeric
Operand | Data Type | Format | Description |
|---|---|---|---|
Source | SINT INT DINT LINT USINT UINT UDINT ULINT REAL LREAL TIME TIME32 LTIME DT LDT | immediate tag | Value to move |
Dest | SINT INT DINT LINT USINT UINT UDINT ULINT REAL LREAL TIME TIME32 LTIME DT LDT | tag | Tag to store the result |
TIP:
See Time and date data types for a complete description of Relative Time (LTIME, TIME,
and TIME32) and Absolute Time (LDT and DT) data types.
TIP:
Keep these restrictions in mind when using Relative Time (LTIME, TIME,
TIME32) and Absolute Time (LDT, DT) data types:
- A relative time type can move only to or from another relative time type.
- And absolute time type can move only to or from another absolute time type. Additionally, you can program an absolute time type with a LINT to accommodate some legacy timestamp practices.
String
Operand | Data Type | Format | Description |
|---|---|---|---|
Source | String type | immediate tag | String to move |
Dest | String type | tag | Tag to store the result |
Affects Math Status Flags
Conditional
See Math Status Flags.
Major/Minor Faults
A minor fault will occur if: | Fault type | Fault code |
|---|---|---|
Overflow detection feature is enabled and the Source value is outside the range
of Dest type. | 4 | 4 |
Execution
Ladder Diagram
Condition/State | Action Taken |
|---|---|
Prescan | N/A |
Rung-condition-in is false | Set Rung-condition-out to Rung-condition-in. |
Rung-condition-in is true | Set Rung-condition-out to Rung-condition-in. The instruction copies the Source into the Dest. String operands: If Source.LEN > SIZE( Dest.DATA) The string is truncated to what will fit S:V is set. |
Postscan | N/A |
Examples
Ladder Diagram

Structured Text
value_2 := value_1;
value_3 := 'Test PASSED';