Motion Servo On (MSO)

Use the Motion Servo On (MSO) instruction to activate the drive amplifier for the specified axis and to activate the axis servo control loop.
Architecture and Safety Support
This instruction cannot be used in a safety task.
Available Languages
Ladder Diagram
MSO_LD_avail_v31
Function Block
This instruction is not available in function block.
Structured Text
MSO(Axis,MotionControl);
Operands
Ladder Diagram and Structured Text
Operand
Type
Compact GuardLogix 5380, CompactLogix 5380, and CompactLogix 5390 controllers
Type
ControlLogix 5580, GuardLogix 5580, and ControlLogix 5590 controllers
Format
Description
Axis
AXIS_CIP_DRIVE
AXIS_CIP_DRIVE
AXIS_GENERIC_DRIVE
AXIS_SERVO
AXIS_SERVO_DRIVE
tag
Name of the axis on which to perform operation. For controllers that support the REF_TO motion data types, the supported axis operand type can be replaced by an equivalent REF_TO type.
Motion Control
MOTION_INSTRUCTION
tag
Structure used to access instruction status parameters.
See Structured Text Syntax for more information on the syntax of expressions within structured text.
Mnemonic
Description
.EN (Enable) Bit 31
It is set when the rung makes a false-to-true transition and remains set until the servo message transaction is completed and the rung goes false.
.DN (Done) Bit 29
It is set when the axis’ servo action has been successfully enabled and the drive enable and servo active status bits have been set.
.ER (Error) Bit 28
It is set to indicate that the instruction detected an error, such as if you specified an unconfigured axis.
Description
The MSO instruction directly activates the drive and enables the configured servo loops associated with a physical servo axis. It can be used anywhere in a program, but should not be used while the axis is moving. If this is attempted, the MSO instruction generates an Axis in Motion error.
The MSO instruction automatically enables the specified axis by activating the drive and by activating the associated servo loop. With a non-CIP axis, the resulting state of the axis is referred to as the Servo Control state. With a CIP axis, the resulting state of the axis is referred to as the Running state.
The most common use of this instruction is to activate the servo loop for the specified axis in its current position in preparation for commanding motion.
IMPORTANT: The instruction execution may take multiple scans to execute because it requires multiple coarse updates to complete the request. The Done (.DN) bit is not set immediately, but only after the request is completed.
In this transitional instruction, the relay ladder, toggle the Rung-condition-in from cleared to set each time the instruction should execute.
Affects Math Status Flags
No
Major/Minor Faults
None specific to this instruction. A major fault can occur if an uninitialized reference or a reference of the incorrect type is passed to the Axis operand. See Common Attributes for operand-related faults.
Execution
Ladder Diagram
Condition/State
Action Taken
Prescan
The .EN, .DN, and .ER are cleared to false.
Rung-condition-in is false
The .EN bit is cleared to false if the .DN or .ER bit is true.
Rung-condition-in is true
The .EN bit is set to true and the instruction executes. If the EN bit is set to false, there is no action taken,
Postscan
N/A
Structured Text
Condition/State
Action Taken
Prescan
See Prescan in the Ladder Diagram table
Normal execution
See Rung-condition-in is false, followed by rung is true in the Ladder Diagram table.
Postscan
See Postscan in the Ladder Diagram table.
Error Codes
See Motion Error Codes .ERR for Motion Instructions.
Extended Error Codes
Extended Error Codes provide additional instruction specific information for the Error Codes that are generic to many instructions. See Motion Error Codes .ERR for Motion Instructions. These Extended Error codes help to pinpoint the problem when the MSO instruction receives a Servo Message Failure (12) error message.
Extended Error Code (decimal)
Associated Error Code (decimal)
Meaning
Object Mode conflict (12)
SERVO_MESSAGE_FAILURE (12)
Axis is shutdown.
Process terminated on request (15)
SERVO_MESSAGE_FAILURE (12)
Enable input switch error. (SERCOS)
Device in wrong state (16)
SERVO_MESSAGE_FAILURE (12)
Device State not correct for action. (SERCOS)
MSO Changes to Status Bits
Axis Status Bit
Bit Name
State
Meaning
ServoActionStatus
TRUE
Axis is in Servo Control state with the servo loop active.
DriveEnableStatus
TRUE
The axis drive enable output is active.
Motion Status Bits
None
Examples
Example 1
Ladder Diagram
MSO_LD_ex_v31
Structured Text
MSO(myAxis, myMotionControl);
Example 2
Relay Ladder
MSO_RL_ex2_v36
Structured Text
MSO(Axis_01,MSO_1);