Guidelines for SOVR instructions
Use the
Equipment Sequence
Override (SOVR) instruction to send a HOLD, STOP, or
ABORT command to an Equipment Sequence
, regardless of ownership.
IMPORTANT:
The SOVR instruction is intended for emergencies only. Control
Engineers should use caution when deciding to use it.
Equipment Sequence
Override (SOVR) instruction.Guideline | Details |
Make sure you want to override other owners. | Under most circumstances, use the SCMD instruction to programmatically command an
Equipment Sequence . However, use the SOVR instruction to command an Equipment Sequence under these conditions:
|
Limit execution of the SOVR instruction to a single scan. | Limit the execution of the SOVR instruction to a single scan. Each command
applies to only a specific state or states. Once the Equipment Sequence
changes state, the command is no longer valid. To limit execution, use methods
such as:
|
Avoid making unnecessary command requests if the Equipment Sequence is
generating sequence events. | Unnecessary command requests can flood the event processing buffers and cause you to miss significant events. |