Phase Failure (PFL)

TIP: When using this instruction with ControlLogix redundancy system, outputs controlled by this instruction may not be bumpless during redundancy switchover, if the instruction and phase program are not scheduled in the highest priority task.
Use the PFL instruction as an optional method to signal a failure for an equipment phase.
The PFL instruction sets the value of the failure code for an equipment phase. Use the instruction to signal a specific failure for an equipment phase, such as a specific device has faulted. The PFL instruction sets the failure code only to a value greater than its current value.
This is a transitional instruction. Follow these steps when using it:
  • In ladder logic, insert an instruction to toggle the rung-condition-in from false to true each time the instruction should execute.
  • In a Structured Text routine, insert a condition for the instruction to cause it to execute only on a transition.
PFL_Other_Pg455_v31
Available Languages
Ladder Diagram
PFL_LD_avail_v31
Function Block
This instruction is not available in function block.
Structured Text
PFL (Failure_Code);
Operands
Ladder Diagram
Operand
Type
Format
Description
Failure_Code
DINT
immediate
tag
Value to set the failure code for the equipment phase.
If a negative failure code given, it evaluates as 0.
Structured Text
The operands are the same as those for the Ladder Diagram PFL instruction.
Guidelines for using the PFL Instruction
Guideline
Details
Put the PFL instruction in the equipment phase.
The PFL instruction sets the failure code for the equipment phase in which the instruction is put. There is
no
operand to identify a specific equipment phase.
Typically, put the PFL instruction in a prestate routine for the equipment phase.
  • The controller always scans the prestate routine, even when an equipment phase is in the idle state.
  • The controller scans the prestate routine before
    each
    scan of a state.
RSL5K_PFL pre and current state routinesV32
Number
Description
1
Prestate routine
2
Current state routine
Use the progress routine to continuously monitor the health of an equipment phase as it progresses through its states.
Prioritize failure codes.
The PFL instruction sets the failure code only to a value greater than its current value.
  • For example, if a PFL instruction sets the failure code = 102, another PFL instruction can only set the failure code > 102.
  • Make sure to assign higher values to exceptions that require higher priority in their handling. Otherwise, a lower priority exception may overwrite a more critical exception.
To take action when a failure occurs, monitor the Failure member of the PHASE tag.
The PFL instruction writes its value to the Failure member of the PHASE tag for the equipment phase.
RSL5K_PFL Description imageV32
Number
Description
1
When creating an equipment phase, the
Studio 5000 Logix Designer
application creates a tag for the status of the equipment phase.
2
controller scope
3
Name =
phase_name
4
PHASE data type
5
The PFL instruction writes its value to the failure member for the equipment phase.
To clear the failure code, use a PCLF instruction.
Use a PCLF instruction to clear the failure code of an equipment phase. Instructions such as a CLR or MOV
will not
change the failure code.
Affects Math Status Flags
No.
Major/Minor Faults
A major fault will occur if:
Fault type
Fault code
Instruction is called from outside an Equipment Phase program.
4
91
See
Index Through Arrays
below for array-index faults.
Execution
For Structured Text, EnableIn is always true during normal scan. Therefore, if the instruction is in the control path activated by the logic, it will execute. All conditions below the thick solid line can only occur during Normal Scan mode.
Condition/State
Action Taken
Prescan
No action taken.
Postscan
No action taken.
EnableIn is false
No action taken.
EnableIn is true
The instruction executes as described above.
Example
Ladder Diagram
In the prestate routine of an equipment phase...
If the
Drain_Valve.FaultAlarm
= 1 (The valve did not go to the commander state.) then
Failure code for the equipment phase = 102.
PFL_LD_ex1_v31
If
Drain_Tank.Running
= 1 (The
Drain_Tank
equipment phase is in the running state.)
And
Drain_Tank.Failure
= 102 (failure code for the equipment phase)
Then
Change the state of the
Drain_Tank
equipment phase to holding via the hold command.
PFL_LD_ex2_v31
Structured Text
In the prestate routine of an equipment phase...
RSL5K_PFL Structured Text
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal