Function Overloading
Function overloading defines two or more functions with the same name but different signature, such as argument or return type. FBD Functions that support overloading take a range of input data types. The output data types depend on the input data types.
FBD Functions follow these rules:
- Input type promotion
- Input type promotion
- Data types rankings from highest to lowest priority:LREAL, REAL, ULINT, LINT, UDINT, DINT, UINT, INT, USINT, SINT
- All inputs promote to the data type of the input with the highest rank before execution
- If all inputs have a rnak value of DINT or lower, all inputs promote to DINT type before execution
- Output type depends on the input typeThe function's output type is the promoted input type
For example, Add function,
- SINT + UINT inputs promote to DINT + DINT inputs. Outputs are DINT
- USINT + LINT inputs promote to LInt + LINT inputs. Outputs are LINT
- UNIT + LREAL inputs promote to LREAL + LREAL inputs. Outputs are LREAL