Find String (FIND)
The FIND instruction locates the starting position of a specified string within another
string.
Available Languages
Ladder Diagram

Function Block
This instruction is not available in function block.
Structured Text
FIND (Source,Search,Start,Result);
Operands
There are data conversion rules for mixed data types within an instruction. See Data conversions.
Ladder Diagram and Structured Text
See Structured Text Syntax for more information on the syntax of expressions within structured
text.DescriptionThe FIND instruction searches the Source string for the Search string. If the
instruction finds the Search string, the Result shows the starting position of the Search
string within the Source string. Otherwise the Results is zero.Affects Math Status
FlagsNoMajor/Minor Faults
None specific to this instruction. See Common Attributes for
operand related faults.
Operand | Type | Format | Description | Notes |
|---|---|---|---|---|
Source | ANY_STRING | Tag | The string to search in | String types are: default STRING data type with max 82 length of characters for the string. any new string type you created with configurable length of characters for the
string. |
Search | ANY_STRING | Tag | The string to find | |
Start | SINT INT DINT | Immediate tag | The position in Source to start the search | Enter a number between 1 and the DATA size of the Source. |
Result | DINT SINT INT | Tag | The position in Source where search string was found |
A minor fault will occur if: | Fault Type | Fault Code |
|---|---|---|
The LEN value of the string tag is greater than the DATA size of the string
tag. | 4 | 51 |
The Start value is invalid, or the Source string is empty. | 4 | 56 |
Execution
Ladder Diagram
Structured Text
Example
Condition | Action |
|---|---|
Prescan | N/A |
Rung-condition-in is false | N/A |
Rung-condition-in is true | The instruction executes. |
Postscan | N/A |
Condition | Action |
|---|---|
Prescan | See Prescan in the Ladder Diagram table |
Normal execution | See Rung-condition-in is true in the Ladder Diagram table. |
Postscan | See Postscan in the Ladder Diagram table |
A message from a
MessageView
terminal contains several pieces of information. The
backslash character (\) separates each piece of information. To locate a piece of information,
the FIND instruction searches for the backslash character and records its position in
find_pos.Ladder Diagram

Structured Text
IF MV_read.EM THEN
FIND(MV_msg,find,1,find_pos);
MV_read.EM := 0;
END_IF;