Module Data Types 1797-IBN16
The table below lists and describes the module-defined data types for the 1797-IBN16 module. It includes information for input (as indicated by an "I") and configuration (as indicated by a "C").
TIP:
FLEX I/O is based on 16-bit INTs and not 32-bit
DINTs. Using 16-bit INTs in instructions that are optimized for 32-bit DINTs may decrease
performance with certain instructions.
Module-defined Data Type: AB:1797_IBN16:I:0
Member Name | Type | Default Display Style | Description |
Fault | DINT | Binary | Fault - Used for Input Data Validation0 = Valid Data1 = Invalid Data - if the connection to the module has been lost, or if the module has a severe hardware fault, the lower 8 bits are set to 1. |
Data | INT | Binary | Input Data - Input data for the module. |
FaultOrCounter | INT | Binary | Depending on the value of FaultEnable, the module either returns input fault status data or the accumulated counts detected by input point 15. |
Fault_0 through Fault_15 | BOOL | Decimal | Members that comprise the FaultOrCounter member above. |
Module-defined Data Type: AB: 1797_IBN16:C:0
Member Name | Type | Default Display Style | Description | |||||||
Config | INT | Binary | Configuration data. | |||||||
Filter_0 Filter_1 Filter_2 | BOOL | Decimal | Input Points 0 – 11 (and internal module fault alarms for input points 0 – 15) Specifies the filter applied to the input points 0-11 and to the fault alarms for input points 0-15. The fault alarms are on a per point basis and are in the input image for the module. This filter cannot be disabled. | |||||||
Filter_3 Filter_4 Filter_5 | BOOL | Decimal | Input Points 12 – 15 Specifies the filter to be applied to the input points 12-15. This filter cannot be disabled, except for input point 15. | |||||||
The Input Filter Time values for this module are shown below.
TIP:
The Input Filter Time also applies to the
internal module fault alarms for input points 0-15. This filter cannot be
disabled, except for input point 15.
| ||||||||||
(Points 15-12) Filter_5, _4, _3 | (Points 11-0) Filter_2, _1, _0 | Maximum Value | ||||||||
5 | 4 | 3 | 2 | 1 | 0 | |||||
0 | 0 | 0 | 0 | 0 | 0 | 0.25ms | ||||
0 | 0 | 1 | 0 | 0 | 1 | 0.5ms | ||||
0 | 1 | 0 | 0 | 1 | 0 | 1ms | ||||
0 | 1 | 1 | 0 | 1 | 1 | 2ms | ||||
1 | 0 | 0 | 1 | 0 | 0 | 4ms | ||||
1 | 0 | 1 | 1 | 0 | 1 | 8ms | ||||
1 | 1 | 0 | 1 | 1 | 0 | 16ms | ||||
1 | 1 | 1 | 1 | 1 | 1 | 32ms | ||||
FaultEnable | BOOL | Decimal | Specifies whether the FaultOrCounter member in the AB:1797_IBN16:I:0 module-defined data type is used for Fault indications on a per channel basis, or to be used to display the count of Input Point 15 of the same data type. Selecting ‘Counter’ chooses to use FaultOrCounter as a counter. In this mode, the pulses counted by input point 15 are reported in the FaultOrCounter member. Selecting Fault chooses to use FaultOrCounter as a fault indication for each channel on the module. In this mode, wire-off and wire-short faults are reported for each input point. Regardless of the input mode chosen, the module always internally keeps track of alarms and input point 15 counts. The Input Mode selection chooses what is returned from the module to be displayed in the FaultOrCounter member.
TIP:
Fault mode may be selectively enabled or
disabled in groups of 4 input points by hardware through a bank of switches on the
IBN16.
TIP:
The intrinsically safe NAMUR inputs of the
IBN16 require special NAMUR connections; if these connections are not made to the
module, it will report wire-off and wire shorted input faults in Fault
Mode.
| |||||||
ResetCounter | BOOL | Decimal | This check box is always enabled, since the counter may be reset in either Fault or Counter mode. When the check box is checked and the configuration is applied, the counter in the module is reset to zero. The counter will not count until the check box is unchecked and the configuration is again applied. | |||||||
DisableFilter | BOOL | Decimal | Causes the counter input point 15 to be filtered with the same filter parameters chosen for the other inputs. The counter filter may need to be disabled to prevent the counter from missing high frequency pulses. This selection is available in Counter or Fault mode, since the counter filter can be enabled or disabled in either mode, and the counter counts in either mode. | |||||||
Provide Feedback