Math Status Flags
Follow the guidelines in this topic for Math Status Flags.
Description
Controllers | Description |
|---|---|
CompactLogix 5380, ControlLogix 5580, Compact GuardLogix 5380, aGuardLogix 5580, and ControlLogix 5590 controllers | A set of Math Status Flags for accessing directly with instructions. These flags are only updated in ladder diagram routines, and are not tags, and flag aliases are not applicable. |
CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, and GuardLogix
5570 controllers | A set of Math Status Flags for accessing directly with instructions. These flags are updated in all routine types, but are not tags, and flag aliases are not applicable. |
Status Flags
Status Flag | Description (For CompactLogix 5380, ControlLogix 5580, Compact
GuardLogix 5380, GuardLogix 5580, and ControlLogix 5590 controllers) | Description (For CompactLogix 5370, ControlLogix 5570, Compact
GuardLogix 5370, and GuardLogix 5570 controllers) |
|---|---|---|
S:FS First scan flag | The first scan flag is set by the controller:
Use the first scan flag to initialize data for use in later scans. It is also referred to as the first pass bit. | The first scan flag is set by the controller:
Use this flag to initialize data for use in later scans. It is also referred to as the first pass bit. |
S:N Negative flag | The controller sets the negative flag when the result of a math or logical operation is a negative value. Use this flag as a quick test for a negative value. | The controller sets the negative flag when the result of a math or logical operation is a negative value. Use this flag as a quick test for a negative value. Using S:N is more efficient than using the CMP instruction. |
S:Z Zero flag | The zero flag is set by the controller when the result of a math or logical operation is zero. Use this flag as a quick test for a zero value. The zero flag clears at the start of executing an instruction capable of setting this flag. | The controller sets the zero flag when the result of a math or logical operation is zero. Use this flag as a quick test for a zero value. |
S:V Overflow flag | The controller sets the overflow flag when:
Use the overflow flag to verify the result of an operation is still in range. If the data being stored is a string type, S:V is set if the string is too large to fit into the destination tag.
TIP:
If applicable, set S:V with an OTE or OTL
instruction.
Click Controller Properties > Advanced tab > Report Overflow Faults to enable or disable reporting overflow faults.If an overflow occurs while evaluating an array subscript, a minor fault is generated and a major fault is generated to indicate the index is out of range. | The controller sets the overflow flag when:
Use the overflow flag to check that the result of an operation is still in range. A minor fault is generated anytime an overflow flag is set.
TIP:
If applicable,set S:V with an OTE or OTL
instruction.
|
S:C Carry flag | The controller sets the carry flag when the result of a math operation resulted in the generation of a carry out of the most significant bit. Only the ADD and SUB instructions, and not the + and – operators, with integer values affect this flag. | The controller sets the carry flag when the result of a math operation resulted in the generation of a carry out of the most significant bit. |
S:MINOR Minor fault flag | The controller sets the minor fault flag when there is at least one minor program fault. Use the minor fault tag to test if a minor fault occurred. This bit only triggers by programming faults, such as overflow. It is not triggered by a battery fault. The bit clears at the beginning of every scan.
TIP:
If applicable, explicitly set S:MINOR with
an OTE or OTL instruction.
| The controller sets the minor fault flag when there is at least one minor program fault. Use the minor fault flag to test if a minor fault occurred and take appropriate action. This bit is triggered only by programming faults, such as overflow. It is not triggered by a battery fault. The bit clears at the beginning of every scan.
TIP:
If applicable, explicitly set S:MINOR with an
OTE or OTL instruction.
|
IMPORTANT:
The math status flags are set based on the
stored value. Instructions that normally do not affect math status flags might appear to
affect math status flags if type conversion occurs from mixed data types for the
instruction parameters. The type conversion process sets the math status flags.
Expressions in Array Subscripts
Controllers | Description |
|---|---|
CompactLogix 5380, ControlLogix 5580, Compact GuardLogix 5380, aGuardLogix 5580, and ControlLogix 5590 controllers | Expressions do not set status flags based on the results of math operations. If expressions overflow:
|
CompactLogix 5370, ControlLogix 5570, Compact GuardLogix 5370, and GuardLogix
5570 controllers | Expressions set status flags based on the results of math operations. If an array subscript is an expression, the expression and the instruction could generate minor faults. |
TIP:
If an array subscript is too large (out of range), a major fault (type 4,
code 20) generates.