Detach from Equipment Sequence (SDET)
This instruction applies to the
Logix Designer
5580P controllers and to ControlLogix 5590P
controllers. Logix Designer
5580P controllers and ControlLogix 5590P controllers
also support controller redundancy.
TIP:
When using this instruction with
ControlLogix
redundancy system, outputs controlled by this
instruction may not be bumpless during redundancy switchover, if the instruction and
sequence program are not scheduled in the highest priority task.
WARNING:
When using redundancy with an
Equipment Sequence
, sequence execution may not be as expected after switchover if the phase and sequence are not scheduled on the same task.Use the Detach from
Equipment Sequence
(SDET) instruction to relinquish ownership of an Equipment Sequence
. After a program executes an SDET instruction, the program no longer owns the Equipment Sequence
. The Equipment Sequence
is then available for ownership by another program or by FactoryTalk Batch
software. Use the SDET instruction only if the program previously took ownership of an Equipment Sequence
through an Attach to Equipment Sequence
(SATT) instruction.This is a transitional instruction. Follow these steps when using it:
- In ladder logic, insert an instruction to toggle the rung-condition-in from false to true each time the instruction should execute.
- In a Structured Text routine, insert a condition for the instruction to cause it to execute only on a transition.
Available Languages
The SDET instruction is available in these languages.
- Ladder diagram

- Structured text: SDET(SequenceName)
Supported Operands
The SDET instruction uses this operand.
Operand | Type | Format | Description |
Sequence Name | Sequence | name of the Equipment Sequence | Equipment Sequence for which you want to relinquish ownership. |
Arithmetic status flags and fault conditions
Arithmetic status flags are not affected by the SDET instruction. The SDET instruction cannot trigger a fault, so there are no fault conditions for this instruction.
Instruction execution
The table describes the execution steps for SDET instructions.
Condition | Ladder Diagram Action | Structured Text Action |
Prescan | The rung-condition-out is set to false. | No action taken. |
Rung-condition-in is false | The rung-condition-out is set to false. | N/A |
Rung-condition-in is true |
| N/A |
Scan of structured text | N/A | In structured text, instructions execute each time they are scanned. To limit the scan of an instruction, use a qualifier of an SFC action or a structured text construct that includes a condition, such as if, then, or else. |
Instruction execution | The instruction relinquishes ownership of the specified Equipment Sequence . | The instruction relinquishes ownership of the specified Equipment Sequence . |
Postscan | The rung-condition-out is set to false. | No action taken. |