Measure Output Gain and Record Values - FLEX I/O Calibration
    To measure the output gain and record its value:
gain
The ratio of the magnitude of the output signal with respect to that of the input signal.
In a linear equation (y=mx+b), the parameter (m) is used to drive the dependent variable (y) to a specified value when the independent variable (x) is at a maximum.
- Measure the voltages of the channels by using a multimeter.
- Enter the value, for each channel, in theRecorded Reference (Volts)/(mA)column.
- SelectNextto see the results of the output gain calibration.
The software uses the value entered, calculates the error correction and sends the correction to the module.
You may also select:
- Retryif an error occurs and you need to repeat a step in the calibration process.TIP:This button is only enabled when an error occurs.
- Stopto cancel calibration and exit the calibration.
- Helpfor assistance with this tab.