Attach Low Reference Signals - Input - FLEX I/O Calibration
    To attach low reference signals for offset calibration.
offset
The steady-state deviation of a controlled variable from a fixed set point. In a linear function (y=mx+b), the parameter (b) is used to drive the dependent variable (y) to zero when the independent variable (x) is zero.
- Attach a precision voltage/current source to the terminals.
- Set the precision voltage/current source to the correct value.
- SelectNextto perform offset calibration.
The module reads the signal and calibrates.
You may also select:
- Retryif an error occurs and you need to repeat a step in the calibration process.TIP:The button is only enabled with an error occurs.
- Stopto cancel calibration and exit the calibration.
- Helpfor assistance with this tab.
Provide Feedback