DF1 Polling Master Driver diagnostics
Diagnostic counters are available by right-clicking the processor station in the
RSWho
window. Driver diagnostics are found under the General
, AB Diagnostic Counters
, Error Counters
, and Performance
tabs in the tabbed dialog box. Driver diagnostics are modeless, and can remain on the desktop if you minimize RSLinx Classic. The following is the list of diagnostic counters shown and the definition of each.General Tab | |
|---|---|
Command Packets Mailed | Solicited messages placed in the driver queue for transmission. |
Reply Packets Received | Reply packets received from slave stations. |
Unsolicited Replies Mailed | Unsolicited reply packets placed in the driver queue for transmission. |
Unsolicited Messages Received | Total number of unsolicited messages/commands received from stations on the same link as this one (local stations). These are messages that are sent to RSLinx Classic that are not sent to an RSLinx Classic virtual link. |
Fake Packets Handled | Diagnostic packets sent to the driver and replied to. |
Total Bad Packets Received | Bad/Unsupported packets received from kernel driver. |
Unmatched Reply Packets | The number of times a reply packet was received by RSLinx Classic to which there was no associated pending packet. |
Bad Packets | Bad/Unsupported packet received from RSLinx Classic engine. |
Timeouts | Total commands for which no response was received before the specified timeout period. |
Communication Errors with Kernel Driver | Failed calls to RSSERIAL.SYS. |
Packets Canceled | Total number of connected packets and unconnected requests sent that the RSLinx Classic engine attempted to cancel due to a timeout or an application or connection termination. If a response to a canceled request is received at a later time, it is disregarded. |
Packets in Queue | Packets in the user-mode queue waiting to be sent to the kernel driver. |
Unsolicited Packets in Queue | Unsolicited packets in the user-mode queue waiting to be sent to the kernel driver. |
AB Diagnostic Counters Tab | |
|---|---|
Poll Packets (ENQ's) Sent | Number of poll packets sent from the master. |
EOT's Received | Number of EOT's received from slave stations (should = ENQ's sent). |
Messages Received | Messages received for other nodes. |
STX's Received | Start of packet (STX) received. |
ACK's Sent | ACK's sent. |
NAK's Sent | NAK's sent. |
Messages Sent | Number of packets placed on the wire. |
ACK's Received | ACK's received. |
Transmit Retries | The packet had a transmit timeout and was retried. |
Timeout on ACK | Timed out waiting for ACK on packet sent. |
Aborted Msgs – Invalid Chars | Invalid characters were received in a packet, so the packet was discarded. |
Bad Characters | Bad characters received. |
Receive Errors (Checksum Failure) | Checksum failed on packet received. |
Duplicate Messages | Duplicates messages received. |
Broadcasts Sent | Broadcast packets sent. |
Messages Received for Other Nodes | Number of packets received for other nodes. |
Error Counters Tab | |
|---|---|
Poll Retries | Number of poll retries. |
Polls That Timed Out and Failed | Polls that timed out and failed. |
Packet Timeouts | Packets that timed out. |
Transmit Retries | Number of transmit retries. |
Transmit Retry Exceeded | The packet failed to transmit the maximum number of times and failed. |
Duplicate Packets Received | A packet with the same TNS as another packet was received. |
Bad Characters Received | Characters were received before a DLE. |
Bad Chars Received After DLE | Invalid characters received in packet. |
DLE Out of Sequence | A DLE was received in an invalid location in the packet. |
DLE STX Wiped Out a Previous Msg | A new packet was received while receiving another packet. |
Illegal State in DF1 State | An internal error caused the driver state machine to enter an invalid state. |
Failed To Transmit Message | A packet failed to be transmitted. |
Modem Dialing Failed | The modem dialer failed to connect. |
Failed to Timeout RSLinx Classic Packet | Packet validation failed on a packet that has timed out. |
CRC Test Failed | CRC checksum failed on a packet received. |
Outstanding Packet Underflow | The driver anticipated more packets than were actually waiting to be sent. |
Outstanding Packet Overflow | Too many packets are waiting to be transmitted to a slave station (maximum is 50). |
Unexpected Packet Received | While waiting for an ACK on a last packet sent, the master received another packet. |
Unexpected CRC Error | CRC checksum failed on a packet received. |
Failed To Transmit Message | The message failed to transmit. |
Retransmit Timeouts | A packet timed out waiting to be retransmitted. |
Unexpected EOT Received | An EOT character was received before the entire packet was read. |
Invalid Receive State | An internal error caused the driver state machine to enter an invalid state. |
Performance Tab | |
|---|---|
Sent Packets/Second | Total packets sent (solicited and unsolicited) per second by user-mode driver. |
Received Packets/Second | Total packets received (solicited and unsolicited) per second by user-mode driver. |