PLC-5: timers, counters, and control files
This addressing syntax applies to PLC-5/10, PLC-5/12, PLC-5/15, and PLC-5/25.
Fnnn:eee.MNE/bb
F | (file type) | |
C | Counter | |
T | Timer | |
R | Control | |
nnn | (file number) | 3-999 decimal |
Timer, counter, and control file types use default file number if the file number is absent. The default numbers are 4 (timer), 5 (counter), and 6 (control). | ||
eee | (element number) | 0-999 decimal |
MNE | (member mnemonic) | |
bb | (bit number) | 0-15 decimal |
Only applies to analog word members. | ||
Example
T57:38.ACC/13 |