Options on the Timing tab of the Control List Selector Properties dialog box

The following table shows the options on the
Timing
tab of the
Control List Selector Properties
dialog box.
Options
Descriptions
Timing and handshaking settings
Enter key control delay
Select the time to delay between the time the operator presses the
Enter
button and the time the application sets the
Enter
connection to 1.
Enter key hold time
Select the time the
Enter
connection will be set to 1. This time setting applies only if the
Enter
connection is assigned and the
Enter Handshake
connection is not assigned.
Enter key handshake time
Select the maximum time the
Enter
connection will be set to 1. This time setting applies only if the
Enter
and
Enter Handshake
connections are both assigned.
Handshake reset type
Select how the
Enter Handshake
connection resets the
Enter
connection to 0:
  • Non-zero value
    resets the
    Enter
    connection when the
    Enter Handshake
    connection is a non-zero value.
  • Zero to non-zero transition
    resets the
    Enter
    connection when the
    Enter Handshake
    connection changes from 0 to a non-zero value.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal