Create a data grid
    Create a grid from data gathered by the event logger.
     TIP: 
    Instead of creating this widget from scratch, you can add 
Alarms Event Logger
 from Template Libraries
 and then modify it accordingly.- Create a data grid:
- InProject view, right-clickMainWindow (type)and select .
 - InProperties, create a dynamic link between theModelvariable and .
 - Create a complex dynamic link:
              - StringFormatter1
 - Format
 - SELECT ActiveState_Id, AckedState_Id, ConfirmedState_Id, Time, Severity, {0:sql_identifier} AS Message FROM "EventLogger1" ORDER BY "Time" DESC
 - {0} StringFormatter1
 - Format
 - Message_{0}
 - {0} DynamicLink
 - {Session}/User/LocaleIds[0]
 
For more information about dynamic links, see Create dynamic links. 
 - Configure data grid columns:
 - Configure the active state column:
- InProperties, double-clickDataGridColumn1and enterActiveState.
 - UnderDataItemTemplate, create a complex dynamic link:
              - KeyValueConverter1
 - Source DynamicLink
 - {Item}/ActiveState_Id
 
For more information about dynamic links, see Create dynamic links. - SetTitletoActive State.
 
 - Configure the acknowledged state column:
- InProperties, next toColumns, selectand select
Text column. - Double-clickDataGridColumn1and enterAckedState.
 - UnderDataItemTemplate, create a complex dynamic link:
              - KeyValueConverter1
 - Source DynamicLink
 - {Item}/AckedState_Id
 
For more information about dynamic links, see Create dynamic links. - SetTitletoAcked State.
 
 - Configure the confirmed state column:
- InProperties, next toColumns, selectand select
Text column. - Double-clickDataGridColumn1and enterConfirmedState.
 - UnderDataItemTemplate, create a complex dynamic link:
              - KeyValueConverter1
 - Source DynamicLink
 - {Item}/ConfirmedState_Id
 
For more information about dynamic links, see Create dynamic links. - SetTitletoConfirmed State.
 
 - Configure the time column:
- InProperties, next toColumns, selectand select
Text column. - Double-clickDataGridColumn1and enterTime.
 - Create a dynamic link betweenTextandNOTE: EnterTimein theInsert the dynamic link sub-path...field.For more information about dynamic links, see Create dynamic links.
 - SetTitletoTime.
 
 - Configure the message column:
- InProperties, next toColumns, selectand select
Text column. - Double-clickDataGridColumn1and enterMessage.
 - Create a dynamic link betweenMessageand .NOTE: EnterMessagein theInsert the dynamic link sub-path...field.For more information about dynamic links, see Create dynamic links.
 - SetTitletoMessage.
 
 - Configure the severity column:
- InProperties, next toColumns, selectand select
Text column. - Double-clickDataGridColumn1and enterSeverity.
 - Create a dynamic link betweenSeverityand .NOTE: EnterSeverityin theInsert the dynamic link sub-path...field.For more information about dynamic links, see Create dynamic links.
 - SetTitletoSeverity.
 
 
Provide Feedback