S7TCP Station

BrowseName
S7TCPStation
SuperType
Communication station(CommunicationStation)

Properties

Name
BrowseName
DataType
Description
Maximum job size in bytes
MaximumJobSizeInBytes
Maximum size of a transmission of tags from the controller (in bytes). Limits both the duration of transmission from the controller and the latency of the write to the controller following the transmission. 0 = maximum value of 243 bytes.
Maximum gap in bytes
MaximumGapInBytes
Maximum distance in bytes between two tags to be part of the same transmission.
IP address
IPAddress
Unique address of the controller on the network.
Port
Port
Number of the port used by the TCP-IP connection. It must match the one configured in the controller.
Timeout
Timeout
Maximum wait time in milliseconds to receive a response from the controller.
Remote device ID
RemoteDeviceId
Default value = 2. This value can influence the type of communication channel (PG or OP) with the controller reserved to the driver: setting it to 1, the driver is assigned a PG communication channel (usually available in limited number and reserved to programming through S7 Manager), while setting it to 2 an OP channel is assigned (OP channels are dedicated to HMI / supervisor communication and are available in greater quantity). Rack Default value = 0. Slot Default value = 2.
Remote rack
RemoteRack
Remote slot
RemoteSlot
Operation code
OperationCode
(Inherited from Communication station)
Tags
(Inherited from Communication station)
Types
(Inherited from Communication station)