Limit alarm

Monitors when the values of interest are reached for variables relating to physical quantities. Activates when the value of the monitored variable reaches one or more limits of interest. When several limits of interest are reached consecutively, the alarm signals only the last limit reached (exclusive) or all the limits reached (non-exclusive).
BrowseName
LimitAlarmController
SuperType
Alarm controller(AlarmController)

Properties

Name
BrowseName
DataType
Description
High-high limit
HighHighLimit
High-high limit value.
High limit
HighLimit
High limit value.
Low limit
LowLimit
Low limit value.
Low-low limit
LowLowLimit
Low-low limit value.
Enabled
Enabled
(Inherited from Alarm controller)
Active
Active
(Inherited from Alarm controller)
Auto acknowledge
AutoAcknowledge
(Inherited from Alarm controller)
Auto confirm
AutoConfirm
(Inherited from Alarm controller)
Input variable
InputValue
(Inherited from Alarm controller)
Message
Message
(Inherited from Alarm controller)
Severity
Severity
(Inherited from Alarm controller)
Last event
LastEvent
(Inherited from Alarm controller)